7. Service & Maintenance

7A. Maintenance

Clean the UPS with a dry cloth after turning off all power to the UPS and switching off the power
switch.

The UPS performs monthly automatic battery tests. However, it is recommended that a 6 month test
be performed on the UPS for battery condition. Perform all tests off peak hours with applications
shut down.

1. Turn off power to the UPS via the branch circuit breaker to the UPS. It is not recommended

to disconnect the plug from the UPS to the utility power due to disconnection of the safety
ground.

2. Allow the UPS to run on battery power for 1 minute. Monitor the UPS for any fault LEDs and

if none are observed, return power to UPS and log results below in the maintenance log. If
battery fault LED is lit, call for service.

Maintenance Log

UPS serial number

Date of installation

Location

Notes

Date

Check

Comments

6th month

12th month

18th month

24th month

30th month

36th month

42nd month

48th month

54th month

60th month

Places to Contact for Service and Questions

In USA or Canada, call 1-800-438-7373 M - F 24 hours. For service outside USA or
Canada, call your local distributor. You may also visit our web site at: www.mgeups.com