MGE UPS Systems 4 User Manual

Page 25

background image

6—3

Options 0, 1, 2 – Extended Battery Configuration

These three option switches should be changed as shown in the table below when new battery
cabinet(s) are added to the UPS. The standard setting for these options are all OFF, selecting
the single/internal battery module option.

Option Setting

Number of battery cabinets installed

0 (A)

1 (B)

2 (C)

Esprit 3 & 4

(SlimLine)

Internal only

*

1

*

2

*

*

3

*

4

*

*

5

*

*

6

*

*

*

7

Indicators: (

*

) = Option On/illuminated ( ) = Option Off/dark

Options 3, 4 – Operating voltage selection

These two options select the nominal operating voltage of the UPS as shown in the table below.
The factory setting is 3=Off, 4=Off, which configures the Esprit for 120V (230V) operation.

Switch Setting

Nominal Operating Voltage

3 (A)

4 (B)

Low Voltage

120 V

*

100 V

*

127 V

*

*

Custom

Indicators: (

*

) = Option On/illuminated ( ) = Option Off/dark

Do not select the "Custom" setting (Option 3 & 4 both ON) unless you are instructed to do so
by MGE service.