Output power rating

AC-input

Voltage

Frequency

Power factor

Output specification

Voltage

Frequency

Harmonic distortion

Overload capability

Battery (sealed lead-acid,
maintenance free)

Environmental and safety

Noise level

Operating temperature

Relative humidity

Safety

EMC

Agency markings

< 50 dBA
0 to 40° C
20 to 90% (without condensation)
UL 1778 / cUL CSA 22.2 N°107.1
FCC 47 CFR Part 15, class A
UL, CSA

6 x 12 V - 9 Ah

6 x 12 V - 7 Ah

Single phase, 60 V / 70 V / 80 V to 142 V (1)
50/60 Hz (auto-select)
≥ 0.95

Pulsar EX 3200RT

3200 VA / 2080 W

Pulsar EX 2200RT

2200 VA / 1540 W

3400753300/AE

- Page 25

(1) Input voltage correspond to 33% / 66% / 100% of the nominal power rating.
(2) Adjustable from 100 V to 127 V using UPS Driver software.
(3) Frequency converter mode may be set using the UPS Driver software.

6.1 Technical characteristics

6. Appendices

Single phase, 120 V ± 3% (2)
50/60 Hz ± 0.5% (3)
< 4% on linear load, < 6% on non linear load
110% continuous, 130% 12s, > 130% 1.5s

Pulsar EXB

2200/3200 RT

72VDC - 18 Ah

Runtime @ full load

20min -40min -60min -80min

1EXB -2EXB -3EXB -4EXB

QUALITY

Designed, Manufactured and
marked under ISO 9001 quali-
ty system.

UL, CSA

FCC Class A

UL ,

cUL

AC INPUT

BATTERY

AC OUTPUT

AC/DC PFC

CONVERTER

DC/AC

INVERTER

DC/DC

PUSH PULL

POWER

SUPPLY

EMI FILTER

EMI FILTER

SAFETY

RELAY

BYPASS

RELAY

BATTERY

CHARGER