beautypg.com

Multiquip MQ Power Whisperwatt 50 Hz Generator DCA-220SSJ User Manual

Page 53

background image

DCA-220SSJ/SSJU— OPERATION AND PARTS MANUAL — REV. #1 (01/06/09) — PAGE 53

1

10.Verify that the Engine Running

status LED on the MPEC unit
(Figure 45) is ON (lit) after the
engine has been started.

3. If any abnor malities exists, the War ning and

Emergency Stop lamps on the Engine Operating Panel
will be lit.

4. Place the

MPEC Control Switch (Figure 42) in the

OFF/RESET position.

5. Place the Diagnostic ON/OFF switch in the ON

position. Verify that an Active Fault Code message is
being displayed (Diagnostic Display Panel). The fault
code message will continued to be displayed until the
fault has been corrected. Figure 43 shown below is a
typical example of an active fault code message (Low
Radiator Coolant).

Figure 44. Engine Speed Switch (High)

When the MPEC Control switch is

placed in the manual position,

preheating of the glow plugs will begin

automatically and the preheat lamp

will stay lit until the

glow plugs are warmed. When the preheat
lamp goes off this signals the completion of
the preheating cycle and the starting of the
engine.

NOTE

Preheat Lamp

9. If the engine is running smoothly, place the engine

speed switch (Figure 44) in the

HIGH” (up) position.

Figure 43. Active Fault Code Message

6. In a situation where several engine problems occur

simultaneously, the word “MORE” appears above the
arrow buttons indicating that there are more fault codes
that need to be viewed. Use the arrow buttons to scroll
to the next active fault code.

If desired, the type of fault code, cause of error and
the countermeasures of the error can be referenced in
a separate engine operator’s manual.

7. Before the engine can be started, the engine fault must

be corrected. Also observe that there are no active
fault codes displayed on the diagnostic panel. If no
fault codes are displayed, place the diagnostic switch
in the OFF position.

13. The generator's AC-voltmeter (Figure 47) will display the

generator’s output in VOLTS. If the voltage is not within
the specified tolerance, use the voltage adjustment
control knob (Figure 48) to increase or decrease the
desired voltage.

Figure 46. Frequency Meter (Hz)

12. The generator's frequency meter (Figure 46) should be

displaying the 50 cycle output frequency in HERTZ.

Figure 45. Engine Running LED (ON)

11. Observe that the Warning and Emergency Stop lamps

on the Engine Operating Panel are OFF.

8. To restart the engine due to error codes, place the

MPEC

Control Switch in the MANUAL position (Figure 42)

Figure 47. Voltmeter

DCA-220SSJ/SSJU — GENERATOR START-UP PROCEDURE (MANUAL)

This manual is related to the following products: