Ta bl e : R e c o m m e n d e d I n p u t / O u t p u t W i r i n g
2- 1
Model
DC Input
AC Output
AC Input
Current
Current
Current
Max.
Current
63054
16 AMPS
5 AMPS
5 AMPS
Min. Wire
Size
(500VA)
12 AWG
14 AWG
14 AWG
Max.
Current
63104
30 AMPS
10 AMPS
10 AMPS
Min. Wire
Size
(1kVA)
10 AWG
14 AWG
14 AWG
Max.
Current
63204
60 AMPS
17 AMPS
17 AMPS
Min. Wire
Size
(2kVA)
8 AWG
12 AWG
12 AWG
NOTE: Maximum circuit breaker rating for AC input shall be
20 Amperes, Maximum DC input current should be limited
to 50 Amperes. Wire gauge for both AC and DC wiring shall
be selected according to the national electrical code.
WARNING
This product is considered permanently connected equipment and
must have a readily accessible disconnect device incorporated in the
fixed wiring.