Ta bl e : L C D R e a d o u t D e f i n i t i o n s
1- 2
Column 1 Column 2
Column 3
Power Source Mode / Status Definition
LED status
Power Source
Source
Source Mode
Status
SYSTEM SET TO THE ON-LINE
Inverter
(INVERTER) MODE.
LED
LINE 1
INV:
on
normal
System is on the inverter delivers power to the load.
Green
LINE 1
INV:
on
dc low
Input DC voltage is less than 42 volts.
Yellow
LINE 1
INV:
on
dc high
Input DC voltage greater than 57 volts.
Yellow
LINE 1
INV:
on
overload
Load greater than 125% of rated VA or Watts.**
Yellow
120% for 2 kVA
LINE 1
INV:
off
DC LOW
On Bypass. Input DC voltage less than 39.5 volts.
Red
LINE 1
INV:
off
DC HIGH
On Bypass. Input DC voltage greater than 60 volts.
Red
LINE 1
INV:
off
DC FAIL
On Bypass. Input circuit breaker turned OFF.
Red.
LINE 1
INV:
off
overload
On Bypass. Load >125%, see specification.
Red
120% for 2 kVA
LINE 1
INV:
off
software
On Bypass. Shut down, micro-processor problem.
Red
LINE 2
BYP:
ready
normal
Input AC voltage in tolerance, ready to go to bypass.
Blink Green
LINE 2
BYP:
ready
ac low
Input AC voltage less than 85% of nominal.
Blink Yellow
LINE 2
BYP:
ready
AC LOW
Input AC voltage less than 71% of nominal.
Blink Red
LINE 2
BYP:
ready
ac high
Input AC voltage greater than 110% of nominal.
Blink Yellow
LINE 2
BYP:
ready
AC HIGH
Input AC voltage greater than 112% of nominal.
Blink Red
LINE 2
BYP:
ready
AC FAIL
Input AC returned, inverter NOT phase locked.
Blink Red
LINE 2
BYP:
ready
ac warn
Input AC less than 85%, inverter phase locked.
Blink Red
SYSTEM SET TO THE OFF-LINE
Bypass LED
(BYPASS) MODE.
LINE 1
INV:
ready
normal
Inverter in stand-by, ready to operate
Blink Green
LINE 1
INV:
ready
dc low
Input DC less than 42 volts.
Blink Yellow
LINE 1
INV:
ready
dc high
Input DC greater than 57 volts.
Blink Yellow
LINE 1
INV:
off
DC LOW
Input DC less than 39.5 volts.
Blink Red
LINE 1
INV:
off
DC HIGH
Input DC greater than 60 volts.
Blink Red
LINE 2
BYP:
static
normal
External AC input powering load. Voltage in
tolerance.
Green
LINE 2
BYP:
ready
ac low
Input AC voltage less than 85% of nom. On
inverter
Yellow
LINE 2
BYP:
ready
AC LOW
Input AC voltage less than 71% of nom. On inverter.
Red
LINE 2
BYP:
ready
ac high
Input AC voltage greater than 110% nom. On
inverter.
Yellow
LINE 2
BYP:
ready
AC HIGH
Input AC voltage greater than 112% nom.
On inverter.*
Red
LINE 2
BYP:
maint
normal
Input DC breaker Off, input AC in tolerance.
Green
LINE 2
BYP:
maint
ac low
Input DC breaker Off, input AC less than 85% nom.
Yellow
LINE 2
BYP:
maint
AC LOW
Input DC breaker Off, input AC less than 72% nom.
Red
LINE 2
BYP:
maint
ac high
Input DC breaker Off, input AC greater than
110% nom.
Yellow
LINE 2
BYP:
maint
AC HIGH
Input DC breaker Off, input AC greater than
112% nom.
Red
LINE 2
BYP:
maint
ac warn
Input DC breaker Off, system recovering from
AC hi/low
Yellow
NOTE: In the maintenance bypass mode, the load will be powered from the input AC source,
independent of its voltage level.
* If inverter failure or DC input loss occurs, and AC input voltage is greater than 112% of nominal, the system will shut down
to protect users equipment.
** If overload is not removed, unit will transfer to Bypass, Inverter Ready will be displayed (see specification).
1 — 6