beautypg.com

General venting – Majestic Appliances 36LDVR User Manual

Page 9

background image

9

LDVR Series Direct Vent Gas Fireplace

10007317

Your fireplace is approved to be vented either through

the side wall, or vertically through the roof.

Only CFM Corporation venting components specifi-

cally approved and labelled for this fireplace may be

used.

Vent terminations shall not be recessed into a wall or

siding.

Horizontal venting which incorporates the twist lock

pipe must be installed on a level plane without an

inclining or declining slope.

Horizontal venting which incorporates the use of flex

venting shall have an inclining slope from the unit of

1” (25 mm) per 24” (610 mm).

General Venting

There must not be any obstruction such as bushes,

garden sheds, fences, decks or utility buildings within

24” (610mm) from the front of the termination hood.
Do not locate termination hood where excessive snow

or ice build up may occur. Be sure to check vent termi-

nation area after snow falls, and clear to prevent ac-

cidental blockage of venting system. When using snow

blowers, make sure snow is not directed towards vent

termination area.
Location of Vent Termination
It is imperative the vent termination be located observ-

ing the minimum clearances as shown on the next

page.
*Check with local codes or in absence of same with

CSAB149.1 Installation Codes (1991) for Canada or fol-

low the current National Fuel Gas Code, ANSI Z223.1/

NFPA 54 for installations in the USA.

POWER CORD

CIRCUIT BOARD

ON/OFF SWITCH
OR
WALL THERMOSTAT

VALVE

RED

WHITE

BLUE

YELLOW

PURPLE

BLACK

WHITE

GREEN

PILOT SENSING

PILOT IGNITER

ORANGE

L1

L2

M
O

P

O

FP1571
SIT822
Synetek wiring
4/05

CLEAR

Fig. 9 SIT822 Valve with Synetek electronic control wiring diagram.

FP1571

This manual is related to the following products: