Majestic Appliances 36LDVR User Manual
Page 28
28
LDVR Series Direct Vent Gas Fireplace
10007317
Troubleshooting - Honeywell Millivolt Valve
Remove Window Frame Assembly Before Service Work
START
CHECK
Gas Supply On
▼
▼
▼
▼
▼
Pilot Lights With Piezo
Ignitor
•
Lockout Has Engaged. Wait 60
Seconds And Try Again.
•
For Spark At Electrode While
Depressing Piezo
1/8" Gap To Pilot Hood Needed.
•
All Wiring Connections
•
Replace Piezo Ignitor
•
Supply Line Hooked Up
•
Shutoff Valve Open
Pilot Stays Lit
•
For Air In The Lines
•
Thermopile Needs A Min.
325mv. Adjust Pilot Flame
Height.
•
All Wiring Connections
•
Replace Thermopile
•
Thermocouple Needs A Min. Of
14mv
•
Defective Valve. Turn To Pilot,
Meter Should Read Greater
Than 100mv. If Not, Replace.
Pilot Lights Main Burner
•
Valve Is Turned On
•
Wall Switch Is Not Turned On.
Watch For Grounded Wires!
•
Thermopile Needs A Min. 325mv.
•
Plugged Burner Orifice
SYSTEM OK
▼
YES
NO
NO
▼
NO
▼
NO
YES
YES
YES