inspectiOn/setup
geNeRal iNspecTiON pRiOR TO OpeRaTiON
ground power Tools
When using power tools or electrical equipment requireing
AC power from the generator, make sure power tool cord
has a ground pin or is double insulated as shown in Figure 5.
Figure 5. Ground Pin
extension cable
When electric power is to be provided to various tools or
loads at some distance from the generator, extension cords
are normally used. Cables should be sized to allow for
distance in length and amperage so that the voltage drop
between the generators and point of use (load) is held to
a minimum. Use the cable selection chart (Table 3) as a
guide for selecting proper cable size.
main circuit Breaker
alWaYs place the main circuit breaker in the OFF position
prior to starting the engine.
NOTICE
Double-insulated power tools and small appliances
have specially insulated housings that eliminate the
need for a ground pin. These types of double-insulated
power cords are designed so that no part of the device
will be electrically live even if the internal insulation fails.
daNgeR
NeveR use power tools or equipment that do not
have a ground capability, the possibility exists of
electrocution, electrical shock or burn, which can cause
severe bodily harm or even
deaTh!
Table 3. cable selection (60 hz, single phase Operation)
current in
amperes
load in Watts
maximum allowable cable length
120 volts
240 volts
#10 Wire
#12 Wire
#14 Wire
#16 Wire
2.5
300
600
1000 ft.
600 ft.
375 ft.
250 ft.
5
600
1200
500 ft.
300 ft.
200 ft.
125 ft.
7.5
900
1800
350 ft.
200 ft.
125 ft.
100 ft.
10
1200
2400
250 ft.
150 ft.
100 ft.
15
1800
3600
150 ft.
100 ft.
65 ft.
20
2400
4800
125 ft.
75 ft.
50 ft.
cauTiON: Equipment damage can result from low voltage.