Installation instructions, Site requirements, Flue and chimney requirements – Stovax VFC Radiant & Convector Fire Range User Manual

Page 9: Installation of the gas supply, Ventilation, Appliance location

background image

9

The flue must be installed in accordance with all local and

national regulation and the current rules in force.

1.FLUE AND CHIMNEY REQUIREMENTS

1.1 The chimney or flue system must comply with the rules in

force, and must be a minimum of 178mm (7î) in diameter.

1.2 The minimum effective height of the flue or chimney must be

3 m (10ft).

1.3 The chimney or flue must be free from any obstruction. Any

damper plates should be removed or secured in the fully open

position, and no restrictor plates should be fitted.

1.4 The chimney should be swept immediately prior to the

installation of the appliance - unless it can be seen to be clean

and unobstructed throughout its entire length.

1.5 Ensure that there is a smooth taper transition from the

fireplace opening into the chimney or flue.

1.6 The flue pull should be checked prior to installation of the

appliance. Apply a smoke pellet to the flue or chimney

opening and ensure that the smoke is drawn into the opening.

If there is not a definite flow, pre-heat the chimney for a few

minutes and re-test the flow.

IF THERE IS STILL NO DEFINITE FLOW, THE CHIMNEY

MAY REQUIRE ATTENTION- SEEK EXPERT ADVICE.

2. INSTALLATION OF THE GAS SUPPLY

2.1 Before installation, ensure that the local distribution

conditions (identification of the type of gas and pressure) and

the adjustment of the appliance are compatible.

2.2 Ensure that the gas supply is capable of delivering the

required amount of gas, and is in accordance with the rules in

force.

2.3 Soft copper tubing and soft soldered joints can be used but

must not be closer than 50mm (2”) to the underside of the

firebox.

2.4 A means of isolating the gas supply to the appliance must be

provided independent of any appliance control.

2.5 All supply gas pipes must be purged of any debris that may

have entered, prior to connection to the appliance.

3. VENTILATION

It is important to ensure that any national ventilation

requirements are taken into account during the installation of

this appliance.

3.1 Ventilation requirements differ according to the model.

Minimum permanent effective free air requirements - if this is

the sole gas appliance in the room - are as follows:

Model No.

Description

Min. vent cm2

8300UC, P8300UC 16” VFC Radiant

8305UC, P8305UC 18” VFC Radiant

100 See note b.

8310UC, P8310UC 22” VFC Radiant

8301UC, P8301UC RD VFC Radiant

NONE

8421UC, P8421UC RD VFC

NONE

8463UC, P8463UC Convector

See notes a & b

8420UC, P8420UC 16” VFC

15

8461UC, P8461UC Convector

8425UC, P8425UC 18” VFC

20

8466UC, P8466UC Convector

8430UC, P8430UC 22” VFC

30

8471UC, P8471UC Convector

See note b

Note a:

Gas input is less than 7kW and flue products clearance under 70

m3/hr. Some countries call for 100cm2 ventilation. Check local

standards.

Note b:

It is essential to check for flue clearance (see diagrams 17/18) If

spillage is detected, it may be necessary to provide additional

ventilation.

3.2 The above table is in addition to any openable window, and

although it must communicate with the outside air, wherever

possible, it can communicate with an adjacent room provided

that the space has a similar vent to the outside.

AIR VENTS MUST NOT BE RESTRICTED.

4. APPLIANCE LOCATION

4.1 This appliance must stand on a non-combustible hearth that is

at least 12mm thick.

4.2 It must be fitted into a non-combustible opening.

4.3 These appliances must be hearth mounted into a fireplace

opening conforming to National Standards. The minimum

dimensions shall be as shown in diagram 1A for VFC Radiant

fires or diagram 1B for VFC Convector fires. (The shaded area

must be flat and square).

INSTALLATION INSTRUCTIONS

SITE REQUIREMENTS

1A