IGNITION CONTROL DIAGNOSTIC INDICATOR CHART

HEATING TIMING CHART

0 15 22 45 52 0 29 120, 135,150

180*PG1348,60 ONLY

Circulator
Blower

On

Off

Seconds

Gas Valve

Igniter

Induced
Draft
Blower

Thermostat

On

Off

On

Off

On

Off

On

Off

Legend: *PG10,12,24-60, *PG1324-42

*PG1348,60

100 %
50 %

COOLING TIMING CHART

Seconds 0 7 30 0 60

Circulator
Blower

Outdoor Fan

and

Compressor

Thermostat

ON

OFF

ON

OFF

ON

OFF

Legend: *PG10,12,24-60, *PG1324-42

*PG1348,60

100 %
50 %

Light Signal

Refer to Abnormal Heating or Cooling Operation Sections of this Manual

Off

Internal Control Failure

1 Flash

External Lockout

2 Flashes

Pressure Switch Stuck Open

3 Flashes

Pressure Switch Stuck Closed

4 Flashes

Thermal Protection Device Open

5 Flashes

Flame Detected with Gas Valve Closed

6 Flashes

Short Cycle Compressor Delay (Cooling Only)