beautypg.com

Exhausting the dryer –31 – GE PFMN445 User Manual

Page 25

background image

25

Installation Instructions

EXHAUSTING THE DRYER

WARNING –

To reduce the

risk of fire or personal injury:

This clothes dryer must be exhausted to the outdoors.
Use only 4″ rigid metal ducting for the home

exhaust duct.

Use only 4″ rigid metal or UL-listed flexible metal

(semi-rigid or foil-type) duct to connect the dryer

to the home exhaust duct. It must be installed

in accordance with the instructions found in

“Connecting the Dryer to House Vent” on page 26

of this manual.

Do not terminate exhaust in a chimney, a wall, a

ceiling, gas vent, crawl space, attic, under an

enclosed floor, or in any other concealed space of

a building.

Never terminate the exhaust into a common duct

with a kitchen exhaust system. A combination of

grease and lint creates a potential fire hazard.

Do not use duct longer than specified in the exhaust

length table. Longer ducts can accumulate lint,

creating a potential fire hazard.

Never install a screen in or over the exhaust duct.

This will cause lint to accumulate, creating a

potential fire hazard.

Do not assemble ductwork with any fasteners that

extend into the duct. These fasteners can

accumulate lint, creating a potential fire hazard.

Do not obstruct incoming or exhausted air.
Provide an access for inspection and cleaning of

the exhaust system, especially at turns and joints.

Exhaust system shall be inspected and cleaned at

least once a year.

This dryer comes ready for rear exhausting. If space

is limited, use the instructions on pages 29–31 to

exhaust directly from the sides or bottom of the

cabinet.

TOOLS AND MATERIALS YOU WILL

NEED TO INSTALL EXHAUST DUCT

rPhillips-head screwdriver

rDuct tape or duct clamp

rRigid or UL-listed flexible

metal 4″ (10.2 cm) duct

rDrill with 1/8″ drill bit

(for bottom venting)

rHacksaw

rVent hood

EXHAUST SYSTEM CHECKLIST

HOOD OR WALL CAP

Terminate in a manner to prevent back drafts or

entry of birds or other wildlife.

Termination should present minimal resistance to

the exhaust airflow and should require little or no

maintenance to prevent clogging.

Never install a screen in or over the exhaust duct.
Wall caps must be installed at least 12″ above

ground level or any other obstruction with the

opening pointed down.

SEPARATION OF TURNS

For best performance, separate all turns by

at least 4 ft. of straight duct, including distance

between last turn and dampened wall cap.

SEALING OF jOINTS

All joints should be tight to avoid leaks. The male

end of each section of duct must point away

from the dryer.

Do not assemble the ductwork with fasteners that

extend into the duct. They will serve as a collection

point for lint.

Duct joints should be made air- and moisture-tight

by wrapping the overlapped joints with duct tape

or aluminum tape.

Horizontal runs should slope down towards the

outdoors 1/4″ per foot.

INSULATION

Ductwork that runs through an unheated area

or is near air conditioning should be insulated

to reduce condensation and lint buildup.

This manual is related to the following products: