Brine Valve PN 3020511
Troubleshooting
Problem
Possible Cause
Solutions
No water refill into the
salt tank
Brine valve not operating
Check that the brine valve is vertical and
moving freely.
Water flow is greater than 1.2 gpm
(4.5 L/m). Replace the refill control
washer with a smaller inside diameter
washer.
Check to see if there is too much air in
the resin tank.
Obstruction in regenerant tube or valve
Inspect pipline, remove any debris.
Damaged brine valve
Replace brine valve.
Excessive refill
Seal leak or failure
Check for debris on seal.
Replace the seal.
The float does not close off incoming water
Float is restricted by the bracket. Raise
top bracket to allow more space for float
movement.
Damaged brine valve
Replace brine valve.
System uses less brine
than the regnerate
setting
Air leak
Inspect pipeline and repair leaks.
Regenerant tube is too long
Be sure the length is less than 6.6 ft (2 m).
Brine valve is set incorrectly
Check and adjust floater to appropriate
height.
Be sure the refill controller is an
appropriate size.
The check ball was pulled at wrong time
Remove the check ball enclosure.