Fvr-c9s-7ux – GE FVR-C9S-7UX User Manual
Page 24
24
FVR-C9S-7UX
Function Code Tables
Function
Code
Function
Date Code Range
Unit
Min.
Set.
Factory
Setting
Change
During
Operation
F15
Motor Running
Sound
0 - 5 (code)
—
—
5
Yes
F16
Fault Memory
The current and previous 3 fault events are displayed
in order of occurrence
—
—
—
No
F17
Data Initialization
0: Inactive
1: Reset to the initial value (value set at factory)
—
—
0
No
F18
Retry
0: Inactive
1: Active (Retry times fixed at 5, Retry starts in
.05s after trip)
—
—
0
No
F19
Motor
Characteristics
0 - 10
—
—
4
Yes
F20
Jump Frequency
Range
0 - 10Hz
Hz
1
3
Yes
F21
Jump Frequency 1
0 - 120Hz
Hz
1
0
Yes
F22
Jump Frequency 2
0 - 120 Hz
Hz
1
0
Yes
F23
Jump Frequency 3
0 - 120 Hz
Hz
1
0
Yes
F24
High Limiter
0 - 100%
%
1
100
Yes
F25
Low Limiter
0 - 100%
%
1
0
Yes
F26
Bias Setting
0 - 100%
%
1
0
Yes
F27
THR Terminal
Function
0: External alarm input
1: Multistep speed selection (X1)
—
—
0
No
F28
BX Terminal
Function
0: Motor coast-to-stop command input
1: Multistep speed selection (X2)
—
—
0
No
F29
Multistep Speed
Setting 1
0.0 - 120 Hz
Hz
1*
10.0 Hz
Yes
F30
Multistep Speed
Setting 2
0.0 - 120 Hz
Hz
1*
20.0 Hz
Yes
F31
Multistep Speed
Setting 3
0.0 - 120 Hz
Hz
1*
30.0 Hz
Yes
F32
Meter Adjustment
0 - 99 (Full scale DC 6.5 - 10.5V)
—
1
85
Yes
F33
Meter Output
selection
0: Output frequency monitor
1: Output current monitor
—
1
0
Yes
*1 Frequency can be set in increments of 0.1 Hz within a range of 0.0 to 99.9 Hz, and can be set in increments of 1 Hz
C92-02