Fvr-c9s-7ux – GE FVR-C9S-7UX User Manual
Page 23
23
FVR-C9S-7UX
Function Code Tables
Function
Code
Function
Date Code Range
Unit
Min.
Set.
Factory
Setting
Change
During
Operation
F00
Data protection
0: Data change possible
1: Data change not possible
—
—
0
No
F01
Frequency
Command
0: Keypad panel (UP/DOWN keys)
1: Analog input (VR, DC0 - 10V or DC4 - 20mA)
—
—
1
No
F02
Operation
Command
0: Keypad panel operation (RUN/STOP keys)
1: External signal operation (FWD/REV terminals)
—
—
0
No
F03
Maximum
Frequency
50 - 120 Hz
Hz
1
60 Hz
No
F04
Base Frequency
50 - 120 Hz
Hz
1
60 Hz
No
F05
Acceleration TIme
0.0 - 60s (0.0 setting = 0.01s)
s
0.1
6.0s
Yes
F06
Deceleration Time
0.0 - 60s (0.0 setting = 0.01s)
s
0.1
6.0s
Yes
F07
Torque Boost
0 - 31 (code)
—
—
13
Yes
F08
Electronic Thermal
Overload Relay
Operation
0: Inactive
1: Active (standard 4-pole motor)
2: Active (forced-air cooled motor)
—
—
0
No
F09
Electronic Thermal
Overload Relay
Level
30 - 105% of rated current of drive
%
1
100%
No
F10
Restart after
Momentary Power
Failure
0: Inactive
1: Active (Restart drive in 0.5s after power failure)
—
—
0
No
F11
Gain for Frequency
Setting Signal
0: For 0 - 10 V
1: For 0 - 5 V
—
—
0
No
F12
DC Brake (Level
Setting)
0 - 100%
—
1
50%
Yes
F13
DC Brake (Time)
0.0 (inactive) 0.1 - 30s
s
0.1
0.1s
Yes
F14
Starting Frequency 1 - 6 Hz
Hz
1
1 Hz
No
C92-01