beautypg.com

Ge digital energy, Ml series, 6 - troubleshooting – GE 500 User Manual

Page 9

background image

OPM_MLE_LTE_350_1K0_1GB_V011

8

DE ML Series: user manual 1.1 (GB)

GE Digital Energy

ML Series

g

Whenever a malfunction occurs, first check external factors (e.g. connections, temperature, humidity or

load) to determine whether the problem is caused by the unit itself or by its environment. Subsequently

check the input fuse: it may be blown. If so: replace the fuse (see 5.2) and be sure that the UPS is not

overloaded.

The following chart is a simple troubleshooting checklist only. If the suggested solution does not succeed,

or if the information is insufficient to solve the problem, please contact your dealer or consult

www.gedigitalenergy.com.

PROBLEM

POSSIBLE CAUSE

SOLUTION

Blown input fuse

Output overload

Reduce load, replace fuse

System failure

Please contact your dealer or

consult www.gedigitalenergy.com

No output voltage during self

test (3.2.2)

System failure

Please contact your dealer or

consult www.gedigitalenergy.com

Only battery start possible

Blown input fuse

See above

No communication between

computer and UPS

Computer interface problem

Check interface cable and

attached computer.

Blown input fuse

See above

UPS operates on battery

though mains is present

Very high, low or distorted

mains voltage

Check mains voltage, contact

qualified electrician

Continuously sounding

buzzer

mains present

UPS overload

Reduce load

Continuously sounding

buzzer

mains not present

UPS overload in battery mode

Reduce load

UPS does not provide the

expected back-up time, no

alarm ‘replace battery’

Weak battery: recent outage or

worn out battery

Charge the battery. If the battery is

near the end of its service life,

consider replacing the battery

even if the ‘replace battery’ alarm

is not yet active.

Battery test just after

installation or mains failure

Allow the UPS to recharge the

batteries

Blinking LED ‘BAT’,

intermittent buzzer

Weak battery

Read 5.3

UPS output switches OFF

Battery depleted during mains

failure: end of runtime

Wait until mains returns

Load is less than 5% of rated

output and no mains power is

present (no-load shutdown

function is active)

Wait until mains returns

Load is more than 150% of

rated output

Reduce load

6 - Troubleshooting

This manual is related to the following products: