3.3.3 On

battery

The UPS uses the energy stored in the batteries: see chapter 7 ‘Batteries - autonomy’.
The UPS will shutdown

after the batteries have been discharged (automatic restart), or

if keypad 'OFF' is pressed for >2 seconds (manual restart required) or

if a 'UPS shutdown' command is given by the computer (automatic restart).

3.3.4 Battery low (end of autonomy)

The batteries are nearly discharged. Controlled shutdown of your computer equipment should be
completed within 1 minute.

3.3.5 Replace

battery

The battery is bad. Perform the self test again (see 3.3.7) to confirm the ‘replace battery’
condition. The alarm only goes out after the next self test: if the battery has either been
sufficiently charged (discharged battery) or replaced by a new one (worn out battery). See also
5.3.

3.3.6 Overload on mains/battery

The demanded power of the equipment exceeds the UPS's rated output power. If the load
exceeds 150% of the rated power:

during battery operation, the UPS output will be switched off immediately

during mains operation, the UPS output will be switched off after 30 seconds.

3.3.7 Self

test

The self test can be started manually: when the UPS operates in mains mode press the ‘ON’
button for 2 seconds. During the test the unit will switch to battery operation for 6 seconds to
check the battery condition. After 6 seconds the unit will switch back to normal operation: mains
mode. See also 3.2.2.


The RS232 port is a plug-in interface port (4-pin, RJ-11, 4P-4C) which enables advanced communication

between the UPS and the computer. Use UPS software for unattended operation of workstations, power

quality related data logging, shutdown notification and control, auto-restart, diagnostics, and battery

conservation features.

We strongly recommend using only original GE Digital Energy™ software in combination with the

RS232 interface port.


For specific information on GE Digital Energy's connectivity products please contact your local dealer or

Internet: www.gedigitalenergy.com

The communication port is available as long as the UPS is ON.

Pin #

Function

1

Tx

2

Rx

3

No connection

4

GND

4 - Communication

RJ-11 4P-4C

ML 350-700

ML 1000