5.1 General

The UPS is virtually maintenance free: take care of proper environmental conditions and keep air inlets-

outlets free of dust. Please read 2.1.

5.2 Fuses

If the AC input fuse (1) is defective, be sure it is replaced by a compatible fuse from the same make and

type. Fuse ratings: see chapter 7.

5.3 Batteries

5.3.1 General

The service life of the battery is up to 6 years.

As a healthy battery is critical to the UPS, keypad 'ON' allows a battery test (3.2.2). When the condition of

the battery is critical, a 'replace battery' alarm will be given (see 3.3). Charge the batteries for at least 10

hours, switch the UPS off and back on, and perform a self test. If the alarm persists replace the batteries

as soon as possible.

5.3.2 Battery replacement

Warning: first read the safety rules in section 1.2.

When replacing the batteries, use the same number and voltage(V)/capacity(Ah).

Proper disposal or recycling of the batteries is required. Refer to your local codes for disposal

requirements.

Never dispose of batteries in a fire: they may explode.

Do not open or mutilate batteries: their contents (electrolyte) may be extremely toxic. If exposed to

electrolyte, wash immediately with plenty of water.

Avoid charging in a sealed container.

Never short circuit batteries. When working with batteries, remove watches, rings or other metal

objects, and only use insulated tools.

Battery replacement procedure (ML 350/500/700)

NOTE: This procedure refers to the ML 350/500/700 models only. The batteries of the ML 1000 are not

user replaceable, please contact your dealer.

1 press keypad “OFF’ and remove the UPS input power cord from the AC mains supply

2 remove UPS front panel (two screws on bottom side)

3 pull out the battery and disconnect the battery wires

4 connect the new battery (black -, red +); small sparks can occur, this is normal

5 reinstall the new battery, do not pinch or clamp the wires

6 reinstall UPS front panel.