beautypg.com

Installation instructions, Connecting dryer using 3-wire connection, 3 exhaust information – GE DCCD330EGWC User Manual

Page 3: Exhaust system check list, Exhaust length

background image

3

Installation Instructions

1. Turn off the circuit breaker(s) (30 amp) or remove the dryer’s

circuit fuse at the electrical box.

2. Be sure the dryer cord is unplugged from the wall.

3. Remove the power cord cover located at the lower back.

4. Install 3/4 in. UL recognized strain relief to power cord

entry hole. Bring power cord through strain relief.

5. Connect power cord as follows:

A. Connect the 2 hot lines to the outer screws of the

terminal block (marked L1 and L2).

B. Connect the neutral (white) line to the center of

the terminal block (marked N).

6. Be sure ground strap is connected to neutral (center)

terminal of block and to green ground screw on cabinet

rear. Tighten all terminal block screws (3) completely.

7. Properly secure power cord to strain relief.

8. Reinstall the cover.

CONNECTING DRYER USING 3-WIRE

CONNECTION

L1

L2

STRAIN RELIEF

BRACKET

3/4", UL

RECOGNIZED

STRAIN RELIEF

HOT

WIRE

HOT

WIRE

GROUND

STRAP

GREEN

GROUND

SCREW

NEUTRAL

(White)

SCREWS

(3)

IF REQUIRED, BY LOCAL CODE,

INSTALL EXTERNAL GROUND

(NOT PROVIDED) TO GROUNDED

METAL, COLD WATER PIPE, OR

OTHER ESTABLISHED GROUND

DETERMINED BY A QUALIFIED

ELECTRICIAN.

COVER

3 #10 AWG MINIMUM COPPER

CONDUCTORS OR 120/240V 30A POWER

SUPPLY CORD KIT MARKED FOR USE

WITH DRYERS & PROVIDED WITH CLOSED

LOOP OR SPADE TERMINALS WITH

UPTURNED ENDS (NOT SUPPLIED).

1. Turn off the circuit breaker (s) (30 amp) or remove the dryer’s

circuit fuse at the electrical box.

2. Be sure the dryer cord is unplugged from the wall receptacle.

3. Remove the power cord cover located at the lower back.

4. Remove and discard ground strap. Keep the green

ground screw for step 7.

5. Install 3/4 in. UL recognized strain relief to power

cord entry hole. Bring power cord through strain relief.

6. Connect power cord as follows:

A. Connect the 2 hot lines to the outer screws of

the terminal block (marked L1 and L2).

B. Connect the neutral (white) line to the center of

the terminal block (marked N).

7. Attach ground wire of power cord with the green ground

screw (hole above strain relief bracket). Tighten all

terminal block screws (3) completely.

8. Properly secure power cord to strain relief.

9. Reinstall the cover.

WARNING: NEVER LEAVE THE

COVER OFF OF THE TERMINAL BLOCK.

WARNING: NEVER LEAVE THE

COVER OFF OF THE TERMINAL BLOCK.

EXHAUST SYSTEM CHECK LIST

HOOD OR WALL CAP

• Terminate in a manner to prevent back drafts or entry of birds or

other wildlife.

• Termination should present minimal resistance to the exhaust air flow

and should require little or no maintenance to prevent clogging.

Never install a screen in or over the exhaust duct. This could cause lint build up.

• Wall caps must be installed at least 12 in. above ground level or any other

obstruction with the opening pointed down.
SEPARATION OF TURNS

For best performance, separate all turns by at least 4 ft. of straight duct,

including distance between last turn and exhaust hood.
TURNS OTHER THAN 90º

• One turn of 45º or less may be ignored.

• Two 45º turns should be treated as one 90º turn.

• Each turn over 45º should be treated as one 90º turn.
SEALING OF JOINTS

• All joints should be tight to avoid leaks. The male end of each section of

duct must point away from the dryer.

• Do not assemble the ductwork with fasteners that extend into the duct.

They will serve as a collection point for lint.

• Duct joints can be made air and moisture-tight by wrapping the

overlapped joints with duct tape.

• Horizontal runs should slope down toward the outdoors ½ inch per foot
INSULATION

Duct work that runs through an unheated area or is near air conditioning

should be insulated to reduce condensation and lint build-up.

3 EXHAUST INFORMATION

WARNING - IN CANADA AND IN THE UNITED

IS 4 IN (102mm). DO NOT USE DUCT LONGER

STATES, THE REQUIRED EXHAUST DUCT DIAMETER

THAN SPECIFIED IN THE EXHAUST LENGTH TABLE.

Using exhaust longer than specified length will:

• Increase the drying times and the energy cost.

• Reduce the dryer life.

• Accumulate lint, creating a potential fire hazard.

The MAXIMUM ALLOWABLE duct length and number of

bends of the exhaust system depends upon the type of duct,

number of turns, the type of exhaust hood (wall cap), and all

conditions noted below. The maximum duct length for rigid
metal duct is shown in the table below.

The correct exhaust installation is YOUR RESPONSIBILITY.

Problems due to incorrect installation are not covered

by the warranty.

EXHAUST LENGTH

4" DIA.

4"

4" DIA.

4" DIA.

2-1/2"

RECOMMENDED MAXIMUM LENGTH

Exhaust Hood Types

Recommended

No. of 90º

Elbows

Rigid

Metal

Rigid

Metal

90 Feet

60 Feet

45 Feet

35 Feet

25 Feet

0

1

2

3

4

60 Feet

45 Feet

35 Feet

25 Feet

15 Feet

Use only for short

run installations

Remove and discard existing plastic or metal foil transition

duct and replace with UL listed transition duct.