Goodman Mfg CPG SERIES User Manual
Page 15
15
Three Phase Models
3) PERCENT VOLTAGE
UNBALANCE
2) MAXIMUM VOLTAGE DEVIATIONS
FROM AVERAGE VOLTAGE
1) AVERAGE VOLTAGE
HOW TO USE THE FORMULA:
EXAMPLE: With voltage of 220, 216, and 213
1) Average Voltage = 220+216+213=649 / 3 = 216
2) Maximum Voltage Deviations from Average Voltage = 220 - 216 = 4
3) Percent Voltage Unbalance = 100 x
=
= 1.8%
Percent voltage unbalance MUST NOT exceed 2%
.
4
216
400
216
= 100 X
F
IELD
D
UCT
C
ONNECTIONS
Verify that all duct connections are tight and that there is no
air bypass between supply and return.
C
ONTROL
V
OLTAGE
C
HECK
With disconnect switch in the open “OFF” position, discon-
nect blue wire from low voltage transformer TRANS1. Close
the disconnect switch to energize TRANS1 control trans-
former. Check primary and secondary (24V) of control trans-
former TRANS1.
T
HERMOSTAT
P
RELIMINARY
C
HECK
With disconnect switch open and blue wire disconnected from
TRANS1 transformer, attach one lead of ohmmeter to termi-
nal R on TB1 terminal block. Touch, in order, the other ohm-
meter lead to terminals Y1, Y2 and G at TB1 terminal block.
There must be continuity from terminal R to terminals Y and
G. R to Y indicates cool. R to G indicates fan (auto). Replace
blue wire on TRANS1 transformer.
F
ILTER
S
ECTION
C
HECK
Remove filter section access panels and check that filters
are properly installed. Note airflow arrows on filter frames.
B
EARING
C
HECK
Prior to energizing any fans, check and make sure that all
setscrews are tight so that bearings are properly secured to
shafts.
S
ET
E
VAPORATOR
F
AN
R
PM
Actual RPM’s must be set and verified with a tachometer or
strobe light. Refer to Appendices A and B for basic unit fan
RPM. Refer also to “Airflow” section of this manual. With
disconnect switch open, disconnect thermostat wires from
terminals Y and W. This will prevent heating and mechanical
cooling from coming on. Place a jumper wire across termi-
nals R and G at TB1 terminal block. Close disconnect switch;
evaporator fan motor will operate so RPM can be checked.
For gas heat units, the airflow must be adjusted so that the
air temperature rise falls within the ranges given stated on
Data Plate (see Appendix A - Blower Performance).
T
ENSION
AND
A
LIGNMENT
A
DJUSTMENT
Correct belt tension is very important to the life of your belt.
Too loose a belt will shorten its life; too tight, premature mo-
tor and bearing failure will occur. Check you belt drive for
adequate “run-in” belt tension by measuring the force required
to deflect the belt at the midpoint of the span length. Belt
tension force can be measured using a belt tension gauge,
available through most belt drive manufacturers.
t = Span length, inches
C = Center distance, inches
D = Larger sheave diameter, inches
d = Smaller sheave diameter, inches
h = Deflection height, inches
DRIVE BELT TENSION ADJUSTMENT
BELT
DRIVE
Used
New
7.5 Ton
2.6 to 3.6
4.5 ± .5 5.5 ± .5
1/4 ± 1/16
8.5
2.6 to 3.6
4.5 ± .5 5.5 ± .5
1/4 ± 1/16
10 Ton
3.0 to 4.0
4.5 ± .5 5.5 ± .5
1/4 ± 1/16
1/4 ± 1/16
1/4 ± 1/16
7.5 Ton
1/4 ± 1/16
8.5
1/4 ± 1/16
10 Ton
1/4 ± 1/16
1/4 ± 1/16
1/4 ± 1/16
12.5 Ton
A, AX
High
Static
3.6 to 4.6
4.9 ± .5 6.0 ± .5
12.5 Ton
2.6 to 3.6
4.5 ± .5 5.5 ± .5
3.0 to 4.0
4.5 ± .5 5.5 ± .5
A, AX Standard
MODEL
DEFLECTION
(in)
DEFLECTION
FORCE (lbs)
SHEAVE
DIAMETER
(in)
TYPE
RECOMMENDED POUNDS OF FORCE PER BELT
The correct deflection force is 5 Ibs. for a new belt and 3.5
Ibs. for a belt that has been run in. New belt tension includes
initial belt stretch. When new V-belts are installed on a drive
the initial tension will drop rapidly during the first few hours.
Check tension frequently during the first 24 hours of opera-
tion. Subsequent retensioning should fall between the mini-
mum and maximum force. To determine the deflection dis-
tance from the normal position, use a straightedge or stretch
a cord from sheave to sheave to use as a reference line. On
multiple belt drives, an adjacent undeflected belt can be used
as a reference.