FS-8700-114 DeviceNet Master Manual

Page 4 of 13

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]

HARDWARE CONNECTIONS

3

The FieldServer is connected to the DeviceNet network as shown in the connection drawing below.

DeviceNet Status LEDs

1

2

3

4

5

FieldServer

DeviceNet Connection Points

V-

V+

To DeviceNet Network

1

2

3

4

5

Pluggable screw 5.08 & 3.84 mm

Connector Pinouts

Pin Signal

Description

Wire color

1

V-

Negative supply voltage black

2

CAN_L

CAN_L Bus line

blue

3

SHIELD Cable Shield

(bare)

4

CAN_H CAN_H Bus line

white

5

V+

Positive Supply Voltage

red

3.1

Hardware Connection Tips / Hints

Use the recommended network cable and terminators as specified by the DeviceNet network organization

and/or the manufacturer of your network equipment.

Terminate each end of the DeviceNet network with a 121 Ω resistor

The bus interface shall be supplied with 24DC ± 10% on the Fieldbus connector