Hardware connections, Hardware connection tips / hints, Hardware connections 3 – FieldServer FS-8700-114 X30 User Manual
Page 4: 1 hardware connection tips / hints
FS-8700-114 DeviceNet Master Manual
Page 4 of 13
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
HARDWARE CONNECTIONS
3
The FieldServer is connected to the DeviceNet network as shown in the connection drawing below.
DeviceNet Status LEDs
1
2
3
4
5
FieldServer
DeviceNet Connection Points
V-
V+
To DeviceNet Network
1
2
3
4
5
Pluggable screw 5.08 & 3.84 mm
Connector Pinouts
Pin Signal
Description
Wire color
1
V-
Negative supply voltage black
2
CAN_L
CAN_L Bus line
blue
3
SHIELD Cable Shield
(bare)
4
CAN_H CAN_H Bus line
white
5
V+
Positive Supply Voltage
red
3.1
Hardware Connection Tips / Hints
Use the recommended network cable and terminators as specified by the DeviceNet network organization
and/or the manufacturer of your network equipment.
Terminate each end of the DeviceNet network with a 121 Ω resistor
The bus interface shall be supplied with 24DC ± 10% on the Fieldbus connector