Appendix B. TROUBLESHOOTING

If there is no 24VDC supply on the DeviceNet Network or if the power supply current is not enough to support the
entire network, then the FieldServer will report that any device configured in the config file is not in the master
scan list, regardless if it is in the scan list or not.

Appendix C. REFERENCE

Appendix C.1. Setting the FieldServer’s DeviceNet MAC ID and Baudrate

The MAC ID and Baudrate can be set in the FieldServer’s CSV file using the System_Station_Address and
DNet_Master_Baudrate parameters or it can be set with DIP switches as depicted below.

Note:

The System_Station_Address parameter must be removed from the configuration file if the DIP switch setting is to
be used.

If System_Station_Address has not been defined in the CSV file, the DIP switch value for both MacID and Baudrate
will be used and the baud parameter in the CSV file will be ignored.