5.3

Client Side Map Descriptor Parameters

5.3.1 FieldServer Related Map Descriptor Parameters

Column Title

Function

Legal Values

Map_Descriptor_Name Name of this Map Descriptor

Up to 32 alphanumeric characters

Data_Array_Name

Name of Data Array where data is
to be stored in the FieldServer

One of the Data Array names from Section 4

Data_Array_Offset

Starting location in Data Array

0 to (Data_Array_Length -1) as specified in Section
4

Function

Function

of

Client

Map

Descriptor.

Wrbc, Wrbx, Rdbc, Arcs. Refer to Error! Reference
source not found.
for more information.

5.3.2 Driver Related Map Descriptor Parameters

Column Title

Function

Legal Values

Node_Name

Name of Node to fetch data from

One of the Node names specified in
“Client Node Descriptor” above

Data_Type

7

Specify memory area. Refer to Appendix
A.1.2
on how to transfer 32 Bit values
using Modbus registers.

Address_Type = ADU
Coil, Discrete_Input, Input_Register,
Holding_Register,

Single_Coil,

Single_Register, Slave_Id
Address_Type = PDU
FC01, FC02, FC03, FC04,
FC05, FC06, FC15, FC16
Address_Type = Modicon_5digit
- (Dash), Single_Register, Single_Coil
All Address_Type
Float_Reg,

32-Bit_Reg,

Input_Float,

Input_Reg_32Bit

Address

Starting address of read block

Address_Type = ADU
1-65536
Address_Type = PDU
0-65535
Address_Type = Modicon_5digit
40001, 30001, etc

Length

Length of Map Descriptor.

1-125 (For Analog polls),
1-800 (For Binary polls).

Write_Length*

Set to Map Descriptor Length if write-thru
operation should write all registers as
specified by length parameter.
By default write-thru writes a single
register.

Map Descriptor Length, 1,

Data_Array_Low_Scale*

Scaling zero in Data Array

Any signed 32 bit integer in the range:

7

Optional only for Modicon_5digit addressing, and only if Single writes do not need to be forced