FS-8700-01 Modbus RTU/ASCIIFS-8700-01_Modbus_RTU.doc Driver Manual

Page 12 of 21

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]

6.2

Server Side Node Parameters

Section Title
Nodes
Column Title

Function

Legal Values

Node_Name

Provide name for Node

Up to 32 alphanumeric
characters

Node_ID

Node ID of physical Server Node

1 – 255

Protocol

Specify protocol used

Modbus RTU

Address_Type

9

Specify Register Mapping Model

ADU,PDU,

-,

Modicon_5digit

Node_Offline_Response*

Set the FieldServer response to the Modbus RTU
Client when the Server Node supplying the data has
gone offline

No_Response,
Old_Data,
Zero_Data,
FFFF_Data,
Refer to Appendix A.2 for
further information.

Node_Description*

Specify Node description text

Any

string

up

to

99

characters long, -


Example

Change protocol to MB_ASCII to use Modbus ASCII protocol

// Server Side Nodes
// For devices where 65536 addresses are available in each memory area.
Nodes

Node_Name

, Node_ID

, Protocol

, Address_Type

MB_Srv_11

, 11

, Modbus_RTU

, ADU

MB_Srv_12

, 12

, Modbus_RTU

, PDU

// For devices where only 9999 registers are available in each memory area.
Nodes
MB_Srv_13

, 13

, Modbus_RTU

, Modicon_5digit

MB_Srv_14

, 14

, Modbus_RTU

, -


9

Optional for Modicon 5 digit devices