Server side node parameters – FieldServer FS-8700-08 User Manual
Page 12
FS-8700-01 Modbus RTU/ASCIIFS-8700-01_Modbus_RTU.doc Driver Manual
Page 12 of 21
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
6.2
Server Side Node Parameters
Section Title
Nodes
Column Title
Function
Legal Values
Node_Name
Provide name for Node
Up to 32 alphanumeric
characters
Node_ID
Node ID of physical Server Node
1 – 255
Protocol
Specify protocol used
Modbus RTU
Address_Type
9
Specify Register Mapping Model
ADU,PDU,
-,
Modicon_5digit
Node_Offline_Response*
Set the FieldServer response to the Modbus RTU
Client when the Server Node supplying the data has
gone offline
No_Response,
Old_Data,
Zero_Data,
FFFF_Data,
Refer to Appendix A.2 for
further information.
Node_Description*
Specify Node description text
Any
string
up
to
99
characters long, -
Example
Change protocol to MB_ASCII to use Modbus ASCII protocol
// Server Side Nodes
// For devices where 65536 addresses are available in each memory area.
Nodes
Node_Name
, Node_ID
, Protocol
, Address_Type
MB_Srv_11
, 11
, Modbus_RTU
, ADU
MB_Srv_12
, 12
, Modbus_RTU
, PDU
// For devices where only 9999 registers are available in each memory area.
Nodes
MB_Srv_13
, 13
, Modbus_RTU
, Modicon_5digit
MB_Srv_14
, 14
, Modbus_RTU
, -
9
Optional for Modicon 5 digit devices