Client side node parameters – FieldServer FS-8700-08 User Manual
Page 7
FS-8700-01 Modbus RTU/ASCIIFS-8700-01_Modbus_RTU.doc Driver Manual
Page 7 of 21
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
5.2
Client Side Node Parameters
Section Title
Nodes
Column Title
Function
Legal Values
Node_Name
Provide name for Node
Up to 32 alphanumeric
characters
Node_ID
Modbus station address of physical Server Node
1-255
Protocol
Specify protocol used
Modbus RTU
Modbus_RTU
Modbus ASCII
MB_ASCII
Port
Specify which port the device is connected to the FieldServer
P1-P8, R1-R2
Address_Type
5
Specify Register Mapping Model
ADU,PDU,
-,
Modicon_5digit
Write_Fnc*
Set to Multiple if Remote Server Node only supports Write Multiple
function code 15 & 16
Multiple, -,
Write_Length*
Set to Map Descriptor Length if write-thru operation should write
all registers as specified by Map Descriptor length.
By default write-thru writes a single register.
If Write_Length also specified on Map Descriptor, Map Descriptor’s
parameter will be used.
Map Descriptor Length, -,
1,
Example:
// Client Side Nodes
// For devices where 65536 addresses are available in each memory area.
Nodes
Node_Name
, Node_ID , Protocol
, Port ,Address_Type
Modbus device 1
, 1
, Modbus _RTU
6
, P1
,ADU
Modbus device 2
, 2
, Modbus_RTU
, P1
,PDU
// For devices where only 9999 registers are available in each memory area.
Nodes
Node_Name
, Node_ID , Protocol
, Port
Modbus device 3
, 3
, Modbus_RTU
, P1
5
Optional for Modicon 5 digit devices
6
Change protocol to MB_ASCII to use Modbus ASCII protocol