FS-8700-01 Modbus RTU/ASCIIFS-8700-01_Modbus_RTU.doc Driver Manual

Page 7 of 21

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]

5.2

Client Side Node Parameters

Section Title
Nodes
Column Title

Function

Legal Values

Node_Name

Provide name for Node

Up to 32 alphanumeric
characters

Node_ID

Modbus station address of physical Server Node

1-255

Protocol

Specify protocol used

Modbus RTU
Modbus_RTU
Modbus ASCII
MB_ASCII

Port

Specify which port the device is connected to the FieldServer

P1-P8, R1-R2

3

Address_Type

5

Specify Register Mapping Model

ADU,PDU,

-,

Modicon_5digit

Write_Fnc*

Set to Multiple if Remote Server Node only supports Write Multiple
function code 15 & 16

Multiple, -,

Write_Length*

Set to Map Descriptor Length if write-thru operation should write
all registers as specified by Map Descriptor length.
By default write-thru writes a single register.
If Write_Length also specified on Map Descriptor, Map Descriptor’s
parameter will be used.

Map Descriptor Length, -,
1,


Example:

// Client Side Nodes
// For devices where 65536 addresses are available in each memory area.
Nodes

Node_Name

, Node_ID , Protocol

, Port ,Address_Type

Modbus device 1

, 1

, Modbus _RTU

6

, P1

,ADU

Modbus device 2

, 2

, Modbus_RTU

, P1

,PDU

// For devices where only 9999 registers are available in each memory area.
Nodes

Node_Name

, Node_ID , Protocol

, Port

Modbus device 3

, 3

, Modbus_RTU

, P1


5

Optional for Modicon 5 digit devices

6

Change protocol to MB_ASCII to use Modbus ASCII protocol