6.3
Server Side Map Descriptor Parameters
6.3.1 FieldServer Specific Map Descriptor Parameters
Column Title
Function
Legal Values
Map_Descriptor_Name Name of this Map Descriptor
Up to 32 alphanumeric characters
Data_Array_Name
Name of Data Array where data is to be
stored in the FieldServer
One of the Data Array names from
Section 4
Data_Array_Offset
Starting location in Data Array
0 to (Data_Array_Length -1) as specified
in Section 4
Function
Function of Server Map Descriptor
Passive
6.3.2 Driver Specific Map Descriptor Parameters
Column Title
Function
Legal Values
Node_Name
The name of the Node
being represented.
One of the Node names specified in Section 6.2
Data_Type
10
Specify memory area
Address_Type = ADU
Coil, Discrete_Input, Input_Register, Holding_Register,
Single_Coil, Single_Register, Slave_ID
Address_Type = PDU
FC01, FC02, FC03, FC04,
FC05, FC06, FC15, FC16
Address_Type = Modicon_5digit
- (Dash), Single_Register, Single_Coil
Length*
Length of Map Descriptor
1-10000, 1
Address
Starting address of read
block
Address_Type = ADU
1-65536
Address_Type = PDU
0-65535
Address_Type = Modicon_5digit
40001, 30001, etc
Data_Array_Low_Scale*
Scaling zero in Data Array
Any signed 32 bit integer in the range:
-2,147,483,648 to 2,147,483,647.
0
Data_Array_High_Scale* Scaling max in Data Array
Any signed 32 bit integer in the range:
-2,147,483,648 to 2,147,483,647.
100
Node_Low_Scale*
Scaling zero in Connected
Node
Any signed 32 bit integer in the range:
-2,147,483,648 to 2,147,483,647.
0
Node_High_Scale*
Scaling max in Connected
Node
Any signed 32 bit integer in the range:
-2,147,483,648 to 2,147,483,647.
100
10
Optional only for Modicon_5digit addressing, and only if Single writes do not need to be forced