The confi guration mode is used to set the RT5 to match your heating/cooling system. The RT5 functions with Friedrich PTAC models.
Ensure that the thermostat is confi gured for air conditioning with ELECTRIC HEAT ONLY.
To confi gure the RT5, perform the following steps:
1. Remove the cover of the thermostat by gently pulling on one of the corners.
2. Simultaneously hold the SW5 and SW6 buttons in for 5 seconds while the RT5 is in OFF mode.
3. Press
the or
button to change settings within each screen.
4. Press
the
SW6 button to advance to the next screen.
Note: The SW5 button will return you to the previous screen.
5. To exit confi guration mode, slide the Mode switch to Heat or Cool.
FILTER
DIFF
ROOM
SET
REMOTE
Configuration Mode
Confi guration Mode Settings
The nine (9) setup screens for Confi guration Mode are as follows:
1. Heat pump and Non Heat Pump – Press the
or
button to confi gure as heat pump, or
non-heat pump system. For heat pumps, there will be an anti-short cycle delay for heating
and cooling
• 0 = Non-heat pump system
Press
the
SW6 button to advance to the next screen.
FILTER
DIFF
ROOM
SET
REMOTE
2. Temperature Scale (F or C) – Choose Fahrenheit or Celsius.
Press
the or
button to select.
Press
the
SW6 button to advance to the next screen.