Column Title
Function
Legal Values
as a time value formatted as hh:mm
(keyword=TIME) or as a string of bytes
(keyword=STRING) or as an occupancy
string (keyword=DOW).
When using the string keyword the driver
reads x consecutive array elements and
treats them like ASCII character values in
forming the response. X is defined by the
length parameter.
Off_String
If the variable has a discrete state, use this
parameter to define the word that describes
the state when the variable’s value is zero. If
you have used one of the above keywords,
simply put a dash in this field.
An ASCII string
which may not
contain spaces.
Length
Always set the length to 1 unless you use the
key word ‘STRING’ as the On_String
parameter.
1
5.3.3.
Timing Parameters
Column Title
Function
Legal
Values
Scada_Hold_Timeout
Specifies time server side waits before responding
to client that node is offline on FieldServer client
side.
>1.0s