FieldServer Carrier DataLink FS-8700-82 User Manual
Page 14
![background image](/manuals/101779/14/background.png)
FS-8700-82 Carrier DataLink
Page 14 of 31
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]
Example
// Server Side Connections
Connections
Port, Baud, Parity, Data_bits, Stop_Bits,
Protocol ,
Handshaking,
Poll_Delay
P8,
9600, None , 8 ,
1 ,
CarrierDL,
None ,
0.100s
5.2.
Server Side Nodes
Section
Title
Nodes
Column
Title
Function
Legal Values
Node_Name Provide name for node
Up to 32
alphanumeric
characters
Node_ID
Modbus station address of physical server node.
These correspond to the ‘devices’ configured in the
DTPConfig. Thus the Node_ID is not the address of
the final CCN device.
The DataLink DTPConfig table maps a device
number (1...15) to a bus number (0-239). Use the
Node_ID to tell the driver which device to use.
1-15
Protocol
Specify protocol used
CarrierDL
Example
// Server Side Nodes
Nodes
Node_Name,
Node_ID,
Protocol ,
Port
FAN1 ,
1 ,
CarrierDL,
It is common to leave Server nodes
unconnected to a port. This means that the
FieldServer can respond with the node’s
data irrespective of which port the request
is received on.