beautypg.com

FieldServer Carrier DataLink FS-8700-82 User Manual

Page 14

background image

FS-8700-82 Carrier DataLink

Page 14 of 31

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]

Example

// Server Side Connections

Connections
Port, Baud, Parity, Data_bits, Stop_Bits,

Protocol ,

Handshaking,

Poll_Delay

P8,

9600, None , 8 ,

1 ,

CarrierDL,

None ,

0.100s

5.2.

Server Side Nodes

Section
Title
Nodes

Column

Title

Function

Legal Values

Node_Name Provide name for node

Up to 32
alphanumeric
characters

Node_ID

Modbus station address of physical server node.
These correspond to the ‘devices’ configured in the
DTPConfig. Thus the Node_ID is not the address of
the final CCN device.
The DataLink DTPConfig table maps a device
number (1...15) to a bus number (0-239). Use the
Node_ID to tell the driver which device to use.

1-15

Protocol

Specify protocol used

CarrierDL


Example

// Server Side Nodes

Nodes

Node_Name,

Node_ID,

Protocol ,

Port

FAN1 ,

1 ,

CarrierDL,

It is common to leave Server nodes
unconnected to a port. This means that the
FieldServer can respond with the node’s
data irrespective of which port the request
is received on.