beautypg.com

Setting the fieldserver node_id, Client side connection descriptions – FieldServer FS-8700-16 User Manual

Page 8

background image

FS-8700-16 BACnet PTP Serial Driver Manual

Page 8 of 32

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: (888) 509-1970 email: [email protected]

4.2

Setting the FieldServer Node_ID

Section Title
FieldServer
Column Title

Function

Legal Values

System_Node_ID Configure Node_ID of FieldServer 1-255


Example

// FieldServer

FieldServer

Title

, System_Node_ID

BACnet_PTP

, 11

4.3

Client Side Connection Descriptions

Section Title
Connections
Column Title Function

Legal Values

Port

Port Name

P1-P8

2

Baud*

Specify baud rate

110; 300; 600; 1200; 2400; 4800; 9600; 19200; 38400; 57600; 115000

Parity*

Specify parity

Odd, Even, None

Data_Bits*

Specify data bits

7, 8

Stop_Bits*

Specify stop bits

1,2

Protocol

Specify Protocol Used BACnet_PTP


Example

// Client Side Connections

Connections

Port

, Baud , Parity , Data_Bits , Stop_Bits , Protocol

P8

, 9600 , Even

, 7

, 1

, BACnet_PTP

2

Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available

on specific hardware.