Server side connection descriptions, Server side node descriptors – FieldServer FS-8700-16 User Manual
Page 13

FS-8700-16 BACnet PTP Serial Driver Manual
Page 13 of 32
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: (888) 509-1970 email: [email protected]
Example
// Data Arrays
Data_Arrays
Data_Array_Name , Data_Array_Format , Data_Array_Length
DA_AI_01
, Float
, 200
DA_AO_01
, Float
, 200
DA_DI_01
, Bit
, 200
DA_DO_01
, Bit
, 200
5.3
Server Side Connection Descriptions
Section Title
Connections
Column
Title
Function
Legal Values
Port
Specify which port the device is connected
to the FieldServer
P1-P8
Baud*
Specify baud rate
110; 300; 600; 1200; 2400; 4800; 9600; 19200;
38400; 57600; 115000
Parity*
Specify parity
None, Odd, Even
Data_Bits*
Specify data bits
7, 8
Stop_Bits*
Specify stop bits
1, 2
Protocol
Specify protocol used
BACnet_PTP
Example
// Server Side Connections
Connections
Port
, Baud , Parity , Data_Bits , Stop_Bits , Protocol
P1
, 9600 , Even
, 7
, 1
, BACnet_PTP
5.4
Server Side Node Descriptors
Section Title
Nodes
Column Title
Function
Legal Values
Node_Name
3
Provide name for node
Up to 32 alphanumeric characters
Node_ID
BACnet station address of physical Server node 1 - 16777215
Protocol
Specify protocol used
BACnet_PTP
Node_Option Enable or disable COV for this node
COV_Enable, COV_Disable
3