beautypg.com

Appendix d.4. bacnet specific statistics – FieldServer FS-8700-16 User Manual

Page 32

background image

FS-8700-16 BACnet PTP Serial Driver Manual

Page 32 of 32

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: (888) 509-1970 email: [email protected]

Appendix D.4. BACnet Specific Statistics

Stat

Description

Resolution

Link Control

A “who-is” link control message was
send or received.

It is normal to receive a few link control
messages. If the number is higher than the
transmit/receive messages, however, there may
be a problem with lost communications..

Unsupported
Properties

A request for an unsupported property
was received

This is not an error. BACnet clients often poll all
properties of a particular object to determine
which properties are supported.

Segmentation
Not Supported

Data was requested but the response
would have exceeded the maximum size
of the APDU and could not be sent using
an un-segmented message.

This is not an error - the BACnet client will use a
different method to read data from the
FieldServer.

Sequence Error

Invoke ID of a reply did not match the
Invoke ID of the poll.

You should not see this message. It normally
indicates a configuration error.

Write

Access

Denied

A write to an object was denied.

This typically happens when trying to write to an
Input Object that is not Out-Of-Service. It is not
possible to write to Input Objects.

Exception Errors

A BACnet Service was denied because it
is not supported

This may be a problem on the Client system.
Consult the PIC statement to determine what
services are supported.