Reversing valve:
Always
de-energized when “Cool” switch is selected on thermostat.
Compressor operation:
If ambient indoor temperature is above set point temperature depending on t-stat differential and
the compressor is not time delayed, turn on compressor. If ambient indoor temperature is
below set point depending on t-stat differential, turn off the compressor.
Compressor time delay:
The
time delay feature is de-energized for a period of time that varies randomly from 180 to
240 seconds. Compressor time delay is initiated every time the compressor is
“off” due to:
(1) Satisfying the temperature set point,
(2) Changing mode to fan only
(3 )Turning the unit off.
(4) Control is first energized or when power is restored after failure
Note: Time delay is disabled during Test Mode.
Indoor coil frost protection (Error Code 07):
While in cool mode: If the indoor coil frost protection sensor reads
30°F for 2 minutes continu-
ously,
turn off the compressor, but continue fan operation. While the compressor is out and the
fan is running: when the indoor coil frost protection sensor reaches
45°F, turn on the compres-
sor. However, the compressor must still wait a standard time of
180 to 240 seconds. While 07
flash, heat operation is disabled.
Fan delay:
This is only for
fan ‘cycle’ mode and not for fan ‘continuous’ mode. When unit cycles cool-
ing ON – start the fan 5 seconds EARLY. When unit cycles cooling OFF – DELAY the fan off
for 30 seconds. Note: the fan delay is disabled during
Test Mode.
Reversing valve: Always de-energized when “Heat” button is pushed.
Compressor operation: Compressor does not operate in this mode.
Electric heat operation: If temp is below set point, depending on t-stat differential, turn on
electric heat. If Ambient is above set point depending on t-stat differential, turn off the electric
heat.
Fan delay: This is only for fan ‘cycle’ mode and not for fan ‘continuous’ mode. When unit
cycles heating
ON – start the fan 5 seconds EARLY. When unit cycles heating OFF – DELAY
the fan off for
15 seconds. Note: the fan delay is disabled during Test Mode.
VPak ELECtRonIC ContRoL BoaRD anD waLL
tHERmoStat SEqUEnCE oF oPERatIon (Continued)
CooL moDE ContRoL FEatURES FoR CooL wItH ELECtRIC HEat UnItS
ELECtRIC HEat moDE ContRoL FEatURES FoR CooL wItH ELECtRIC
HEat UnItS
- 7,200 BTU Packaged Terminal Air Conditioner Warranty 920-087-09 (12/10) 24,000 BTU/h A-SERIES ZoneAire Series 42 Inch Packaged Terminal Air Conditioner Warranty ZoneAire Series 42 Inch Packaged Terminal Air Conditioner Warranty Guide 7,200 BTU Packaged Terminal Air Conditioner Installation and Operation Manual HEAT PUMPS 7,200 BTU Packaged Terminal Air Conditioner Product Profile