beautypg.com

Caution, 1 introduction – Hearth and Home Technologies SL-350TRSI-AUE User Manual

Page 6

background image

6

Heat & Glo • SL-350TRSI-AUE • 2089-902 Rev. B • 6/06

Figure 4. Framing Dimensions

Framing should be constructed

of 2 X 4 lumber or heavier.

The framing headers

may rest on the

fireplace stand-offs.

A

B

C

D*

E*

34"

30-5/8"

16 1/2"

41-3/4"

21-1/4"

(864mm)

( 778mm)

(419mm)

(1060mm)

(540mm)

*NOTE: The center of the framing hole
is one inch (254mm) above the
center of the horizontal flue pipe.

CAUTION:

Measure heater dimensions, and verify

framing methods and wall covering details before fram-
ing construction begins.

1.1 INTRODUCTION

This model is designed to operate with all combus-
tion air being siphoned from the outside of the build-
ing and all exhaust gases expelled to the outside of
the building.

WARNING: THIS UNIT IS NOT FOR USE WITH
SOLID FUEL.

These units MUST use the flue termination described
in the flueing section of the manual.

The control system for this model is an electronic igni-
tion type. It consists of a gas control valve/variable regu-
lator, a pilot/sensor/electrode and an ON/OFF switch.
The controls are located behind the access door. Ro-
tate the door down to open. See Figure 1.

Minimum inlet gas supply pressure for purpose of in-
put adjustment is 4.5 inches w.c. (1.13kPa) for natural
gas and 11 inches w.c. (2.75kPa) for propane. Mani-
fold (outlet) pressures should be set at 3.5 inches w.c.
(.8kPa) for natural gas models and 9.5 inches w.c.
(2.36kPa) for propane models.

A

B

C

D

E

Minimum Clearances

from the Fireplace to Combustible Materials

Inches

mm

Glass Front ...................................... 36 ........ 914

Floor ................................................. 0 ........... 0
Rear ................................................ 1/2 ........ 13
Sides .............................................. 1/2 ........ 13
Top ................................................ 1 1/2 ....... 38

Ceiling* ............................................ 31 ........ 787

*The clearance to ceiling is measured from the top
of the unit, excluding the standoffs (see Figure 34).

For minimum clearances, see the direct vent termina-
tion clearance in Figure 5.

Minimum Clearances

from the Vent Pipe to Combustible Materials

Inches

mm

Vertical Sections. ............. 1 ................ 25
Horizontal Sections
Top ..................................... 3 ................ 75
Bottom ............................... 1 ................ 25
Sides ................................. 1 ................ 25
At Wall Firestops
Top ..................................... 3 ................ 75
Bottom ............................... 1 ................ 25
Sides ................................. 1 ................ 25