6. M-Bus module
The EDC-module as M-Bus module is used for
integration of water meters in wired M-Bus net-
works. The EDC-M-Bus module which is mount-
ed on the water meter enables the reading of the
water meter via Bus.
Cable assignment (polarity protected):
Brown
M-Bus 1
White
M-Bus 2
7. Pulse modules
The pulse modules can be delivered in three dif-
ferent versions (Table 3). Type P1 will be deliv-
ered as a standard.
EDC-Pulse
Type P1:
Type P2:
Type P3:
Output 1:
balanced* pulses
Forward pulses
Forward and reverse pulses
Output 2:
Dismounting module alarm
Reverse pulses
Flow direction (open = forward)
Function of the pulse modules output
* Reverse pulses are reduced by the corresponding number of forward pulses
Cable assignment
Green
Output 1
Yellow
Output 2
Grey
Ground (GND)
General specifications EDC M-Bus:
Number of conductors
2
Cable length
1,5 m
Electromagn.
compatibility
fulfils the European
Directive 89/336 EWG
General specifications EDC pulse
Number of conductors
3
Cable length
1,5 m
Output type N-channel
open-drain
(equivalent to
open-collector)
Max. output voltage
24 VDC
Max. output current
50 mA
Pulse length
≥ 10 ms
Output resistance (open)
110 Ώ
Output capacitance
(closed)
1 nF
Electromagn.
Compatibility
fulfils the European
Directive 89/336/EWG
Standard Pulse value
DN15-40
1 L/Imp.
DN50-125
10 L/Imp.
DN150-200
100 L/Imp
beginning DN300
1000 L/Imp