Technical data flow sensor IUF
Nominal flow qp
m³/h
0,6
1,5
2,5
Maximum flow qs
m³/h
1,2
3
5
Minimum flow qi
l / h
6 / 12 / 24
15 / 30 / 60
25 / 50 / 100
Pressure loss at qp
bar
<= 0,25 bar
Medium temperature range
°C
0°C <= Ɵ q <= 90°C / 0°C <= Ɵ q <= 130°C
Minimum pressure
(to avoid cavitation)
bar
1 bar at qp and 80°C medium temperature range
Measurement accuracy class
3 / 2
Nominal pressure/peak pressure
PS/PN
Body with
threaded connection
16/16
PS/PN
Body with flange/DN
16/16 / 25/25
IP-Protection class
68
Installation position
in any position
Installation
return flow optionally forward flow
Cable length up to calculator
m
1,2
Installation place temperature sensorsd
M10 x 1
Heat carrier (Medium)
Water
Nominal diameter
DN
15
15
20
Connecting threads*
Nominal flow qp
(m³/h)
L [mm]
Threaded
connection
Flange / ND
0,6
110
G¾B
--
0,6
130
G1B
--
0,6
190
G1B
20
1,5
110
G¾B
--
1,5
130
G1B
--
1,5
190
G1B
20
2,5
130
G1B
--
2,5
190
G1B
20
* optionally
Installation manual
General information
With zelsius C5 IUF, you have acquired one of
the most up-to-date, modern heat meters cur-
rently available on the market. By this version,
the water volume is determined based on the
transit time method. The measurement accuracy
is based on the measurement requirements of
EN 1434 class 2, optionally class 3. Expressive
symbols in the display and easy menu naviga-
tion make readout simple. Can be operated with
one single button. It is equipped with a long-life
battery made for operation during the initial veri-
fication validity period (5 years) including a re-
serve of at least another year. The meter can be
equipped optionally with a battery lifetime of 11
years.