ENVISION LOW SILL CONSOLE INSTALLATION MANUAL

consecutive faults occur in 60 minutes during a single

heating or cooling demand, the unit will go into lockout

mode, turning off the compressor, and enabling the alarm

output until the controller is reset. If the control faults

due to the low pressure input (BI-3) being open during

the pre-compressor startup check, the control will go into

lockout mode immediately, disabling the compressor from

starting and enabling the alarm output (BO-6). The lockout

condition can be reset by powering down the controller, by

a command from the BAS, or by the holding the ESC and

Return keys on the MUI for 5 seconds.

Freeze Detection Limit (AI-5)

The freeze detection limit sensor will monitor the liquid

refrigerant temperature entering the water coil in the

heating mode. If the temperature drops below the freeze

detection limit trip point for the recognition delay period,

the condition will be recognized as a fault. The freeze

detection limit trip point will be factory set for 30°F and

will be field selectable for 15°F by removing a jumper wire

on BI-5. The freeze detection limit fault condition will be

bypassed 2 minutes at normal compressor startup, to allow

the refrigeration circuit to stabilize. If the freeze detection

limit sensor becomes unreliable at any time compressor

operation will immediately be suspended until the problem

is corrected. This should be displayed as an alarm on the

BAS and the MUI. This alarm will be reported a “Water Low

Temp Limit” fault.

High Pressure (BI-11)

The high-pressure switch shall be a normally closed (NC)

switch that monitors the systems refrigerant pressure. If

the input senses the high-pressure switch is open it must

disable the compressor output immediately and count the

fault. The compressor minimum on time does not apply if

the high-pressure switch opens. The compressor will not

restart until the compressor short cycle time delay has

been satisfied.

Low Pressure (BI-3)

The low-pressure switch shall be a normally closed (NC)

switch that monitors the systems refrigerant pressure. The

input shall be checked 15 seconds before compressor start

up to be sure the pressure switch is closed and then ignored

for the first 2 minutes after the compressor output (BO-2) is

enabled. If the switch is open continuously for (30) seconds

during compressor operation the compressor output (BO-2)

will be disabled. The compressor will not restart until the

compressor short cycle time delay has been satisfied.

Condensate Overflow

The condensate overflow sensing circuit will monitor

the condensate level as a resistance input to AI-3. If

the condensate water level rises resulting in the input

resistance rising above the set point for the recognition

delay period, the condition will be recognized as a fault.

The condensate will be subjected to a (30) second

lockout delay which requires that the fault be sensed for a

continuous (30) seconds before suspending unit operation.

Alarm Output (BO-6)

The alarm output will be enabled when the control is in the

lockout mode and will be disabled when the lockout is reset.

Test Mode

Raising the zone temperature input (AI-1) reading to 180–

220°F or by holding the ESC and down arrow keys on the MUI

for 5 seconds will put the control into test mode. In test mode

the random start delay and the compressor fixed on delay

time will both be shortened to 5 seconds and the reversing

valve will be allowed to cycle with out shutting down the

compressor. If an MUI is connected to the control LED 8 will

flash and the words “Test Mode Enabled” will be shown on

the LCD display when the control is in test mode. Test mode

will be disabled after a power cycle, 30 minute timeout, or by

holding the ESC and Up arrow keys on the MUI.

Sequence of Operation

Power Fail Restart

When the controller is first powered up, the outputs will

be disabled for a random start delay. The delay is provided

to prevent simultaneous starting of multiple heat pumps.

Once the timer expires, the controller will operate normally.

Random Start Delay

This delay will be used after every power failure, as well as

the first time the compressor is started after the control

exits the unoccupied mode or the emergency shutdown

mode. The delay should not be less than 1 second and not

longer than 120 seconds. If the control is in test mode the

random start delay will be shortened to 5 seconds.

Compressor Fixed On Delay Time

The Compressor Fixed On Delay Time will ensure that the

compressor output (B02) is not enabled for (90) seconds

after the control receives a call to start the compressor.

This delay is adjustable from 30 – 300 seconds over a BAS

or a MUI. If the control is in test mode the Compressor

Fixed On Delay Timer will be shortened to 5 seconds.

Controls cont.