Local access to the control console, User ’s guide, Switched rack pdu – APC Switched Rack Power Distribution Unit (PDU) User Manual

Page 18

background image

®

®

®

®

USER

’S GUIDE

switched rack pdu

14

Local access to the control console

You can use a local computer that connects to the Switched Rack PDU
through the serial port on the front of the unit.

1. Select a serial port at the local computer, and disable any service

which uses that port.

2. Use the supplied serial cable (940-0144) to connect the selected port

to the RJ-12 serial port on the front of the Switched Rack PDU.

3. Run a terminal program (such as HyperTerminal) and configure the

selected port for 9600 bps, 8 data bits, no parity, 1 stop bit, and no flow
control. Save the changes.

4. Press

E

NTER

twice to display the User Name prompt.