Upgrading firmware, User ’s guide, Switched rack pdu – APC Switched Rack Power Distribution Unit (PDU) User Manual

Page 10

background image

®

®

®

®

USER

’S GUIDE

switched rack pdu

6

Upgrading Firmware

0

You can use a local computer that connects to the PDU through the serial
port on the front panel of the unit.

1. Select a serial port at the local computer, and disable any service

which uses that port.

2. Use the supplied serial cable (940-0144) to connect the selected port

to the RJ-12 serial port on the front panel of the PDU.

3. Run a terminal program (such as HyperTerminal) and configure the

selected port for 9600 bps, 8 data bits, no parity, 1 stop bit, and no flow
control. Save the changes.

4. Press

E

NTER

twice to display the User Name prompt.

5. Enter your user name and password (both apc, for administrators only)

and press the

E

NTER

key.

6. From the Control Console menu, select System, then Tools, then

XMODEM.

7. At the prompt Perform transfer with XMODEM-CRC? type

YES

,

and press

E

NTER

.

8. The system will then prompt you to choose a transfer rate and to

change your terminal settings to match the transfer rate. Press

E

NTER

to set the Switched Rack PDU to accept the download.

For a complete description of how to download a firmware
upgrade for your PDU, see the Management Card
Addendum
(.\doc\Addendum.pdf) on the provided APC PDU
Utility CD.