Gillette Generators SPMD-2500 THRU SPMD-4000 User Manual
Page 13
PAGE 13
WARNING: An open bottom, stationary gen-set must be installed over a non-combustible material, such as a
cement slab, and must be positioned to prevent combustible materials, rain, pooling water, sprinklers from
entering into, and accumulating under gen-set.
A) Installation should place gen-set as close as possible to the fuel supply, the transfer switch, and distribution/
circuit breaker panel.
B) Service access must be provided to allow generator housing doors to fully open.
C) Installation must prevent water, leaves, grass, sow, etc., from reaching top of generator skid base. Drainage
must be provided to keep concrete pad, free from standing water.
D) Always remove snow accumulation on roof when snow depth reaches 4”.
E) Maximum ambient operating temperature is 105º F (40ºC),, for all gen-set sizes.
JOHN DEERE DRIVEN,
SPJD GEN-SET MODEL
MTU DRIVEN,
SPMD GEN-SET MODEL
A
A1
A2
A3
A4
E1
EC
IC
HEIGHT
SPJD-250, SPJD-300
68
6
N/A N/A
62
18
14
7
47 1/4
SPJD-420, SPJD-520,
SPJD-600
78
6
N/A N/A
72
18
16
8
53
SPJD-800, SPJD-1000
98
6
49
N/A
92
24
24
12
72 1/2
SPJD-1250, SPJD-1550,
SPJD-1800, SPJD-2100
110
6
55
N/A 104
42
24
12
72 1/2
SPMD-2500, SPMD-2800,
SPMD-3000
132
8
48
84
124
23
30
12
80
SPMD-3500, SPMD-4000
144
9
51
93
435
25
34
16
94
C
36
42
48
48
52
60
B
33
39
45
45
49
57
A1
EC
A2
A4
A
IC
B
C-C
C
A3
E1
Battery Tray
Electrical Stub Up
(Exhaust Chute on
Enclosed Gen-Set)
(Air Intake Chute
on Enclosed
Super-Silent Gen
-Set)