Maintenance – Fulton Edge ICX or FB-F Vertical Tubeless Boilers (Steam), Gas Fired User Manual
Page 70
61-G 1/01
Maintenance
Problem
Cause
Remedy
Poor Combustion
1. Refractories
Check refractories to see if they are plugged with soot or
broken in pieces. Clean or replace as necessary.
2. S.S. Ring
Check to be sure ring is present and fits tight against the
furnace wall (50-100 HP).
3. Primary Air
Check air adjustment. Air/fuel mixture may be off. Open
Adjustment
primary air so fire is to outside wall of furnace.
4. Secondary Air
Check main air adjustment to see if it is loosened up.
Adjustment
Adjust as necessary and tighten plate in position. Check
CO
2
and O
2
levels.
5. Draft
Check draft with a gauge. Draft should be a -.02 " to -.04"
W.C. with burner off or -.04" to -.06" when operating. May
need to install a barometric damper.
6. Dirty Flue
Check flue for carbon buildup or blockage. Clean flue
passages with brush.
7. Negative Room Pressure
Make sure no exhaust fans are running in the boiler room.
Burner back fires
1. Refractories
Check refractories to see if they are plugged with soot or
broken in pieces. Replace as necessary.
2. Ignition Electrodes
Check electrodes for carbon buildup and clean if
necessary. Check for proper adjustment Readjust if
necessary. Check for cracks in porcelain; if found replace.
3. Flame rode adjustment
Check flame rod for carbon buildup and clean if
or UV Scanner
necessary. Check flame rod adjustment via a
display module. Flame signal should be 5 VDC.
Check for cracks in porcelain. If found, replace.
Check for dirt on flame scanner and clean.
Check for proper location of detector.
5. Draft
Check draft with a gauge. Draft should be a -.02 " to -.04"
W.C. with burner off or -.04" to -.06" when operating. May
need to install a barometric damper.
6. Negative Room Pressure
Make sure no exhaust fans are running in the boiler room.
Boiler will not
1. Gas Supply
Check gas pressure coming into gas train. If low,
maintain pressure
contact gas company. Should be 7" to 11" W.C. Check
coil in gas valve with AMP meter. Replace if bad.
Check gas regulator setting and readjust as necessary.
2. Dirty Flue
Check flue for carbon buildup or blockage. Clean flue
passages with brush.
3. Pressuretrol
Disconnect all power to the controller. Disconnect the
wires from the controller. Put an OHM meter between the
switch terminals. Lower the set point of the controller.
Switch should make. Raise the set point and recheck
with OHM meter. Switch should break. If the controller
operates improperly, replace it.