beautypg.com

Lsi-16 specifications – Biamp LSI-16e User Manual

Page 16

background image

16

LSI-16 SPECIFICATIONS

Life Safety Interface 16 SPECIFICATIONS

System Fault Relay:

Type:

Load:
Maximum operating voltage:
Maximum operating current:
Maximum switching capacity:
Minimum permissible load:

Single ‘Form C’ voltage-free SPST

change-over contact

Resistive

125VAC, 60VDC

600mA AC, 1A DC

37.5VA, 30W

10µA @ 10mVDC

RS232 Port

Type:
Baud Rate:

DTE

57600

Connection:

RJ45 with shielded Ethernet/PoE cable

(CAT5, CAT5e, CAT6, or CAT7)

Control Inputs:

Number:
Type:
Cathode presented at input –
pull low to enable. Sink Current:
Min:
Max:
Maximum Terminal Voltage:
Isolation:

Eight

Opto Isolator LED

1mA
6mA

24V

3kV

Power:

Main:
PoE:

24V DC 15W

802.3af Class 3

Base Dimensions:

Height:
Width:
Depth:

1.75 inches (44.5mm)

19 inches (483mm)

10 inches (254mm

Monitored I/O:

Number:
Type:

Maximum Continuous Current:
Current Limit:
Maximum External Supply:
VMon Input Shutdown:

Eight

FET switch, open drain

(low side driver)

0.35A

0.8A

35V
35V

Weight:

Approx 6.4 lbs. (2.8kg)

Ambient Operating
Temperature Range:

32-113 degrees F (0-45 degrees C)

Compliance:

FCC Part 15, class B

EC marked

EN 54-16 certified

RoHS Directive

UL 60065 Listed, E215636

C-UL Listed, E215636

C-Tick, N24138 (Australia)

Life Safety Interface 16 BLOCK DIAGRAM

LEDs

Vocia

System

24V DC

PoE

8 Control Inputs

8 Monitored Outputs

IM-16 (optional)

ID Switches

Host Processor

This manual is related to the following products: