beautypg.com

IMP Pumps NMT(D) 40-100 & NMT SAN flanges User Manual

Page 16

background image

GB

-16-

1. G

eneral

i

nfOrmatiOn

1.1

U

ses

The circulating pumps of the mentioned types are used for the transfer of liquid media within

the system of hot-water heating, air-conditioning and ventilation. They are designed as single

or twin variable-speed pumping aggregates where the speed is regulated by electronic device.

They are to be used with pure water or glycol/water mixture.

1.2

T

echnical

daTa

1.2.1

p

ump

labeling

1.2.2

c

OnnectiOn

and

electrical

data

Power ratings

NMT 40

NMT 50

NMT 65 NMT80/100

Rated voltage (U)

230V AC ±15%, 47-63Hz

Pumps can operate at reduced voltage with limited power

P=Imax*U.

Rated power (P)

500W

800W

1100W

1600W

Rated current

2.2A

3.5A

4.8A

7.0A

Current limit (Imax)

6A

8A

Startup

Built-in startup circuit.

standards and protection

Protection class

IP44

Insulation class

180 (H)

Motor protection

Thermal - built in

Medium temperature

-10°C do 110°C

Ambient temperature

0°C do 40°C

1

Water quality

VDI 2035

Rated pressure

6/10 bar

EMC (89/336 EEC)

EN 61000

LVD (73/23/EC)

EN 60335-1

EN 60335-2-51

Machine safety (98/37/EC)

EN ISO 12100

1

Ambient temperature should be 25°C or lower when medium exceeds 80°C.