Ground the switch – Rockwell Tools STRATIX 8000 ETHERNET 1783-MS10T User Manual
Page 38
38
Publication 1783-UM002C-EN-P - April 2009
Chapter 2
Ground the Switch
Follow these steps to connect the switch to a protective ground.
1.
Use a standard Phillips screwdriver or a ratcheting-torque screwdriver
with a Phillips head to remove the ground screw from the front panel of
the switch.
2.
Store the ground screw for later use.
3.
If your ground wire is insulated, use a wire stripping tool to strip the 5.3
mm
2
(10 AWG) ground wire to 12.7 mm (0.5 in.) ± 0.5 mm (0.02 in.).
4.
Insert the ground wire into the ring terminal lug.
ATTENTION
For proper grounding, you must always connect the power
supply functional-ground screw when connecting the power
supply. You must provide an acceptable grounding path for each
device in your application. For more information on proper
grounding guidelines, refer to publication
, Industrial
Automation Wiring and Grounding Guidelines.
ATTENTION
You must use the external grounding screw on the front of the
switch to ground the switch. Use a 5.3 mm
2
(10 AWG) ground
wire.
31789-M
12.7 mm (0.5 in.)