beautypg.com

3 write multiple registers (0x10), Write multiple registers (0x10) – Hamilton Sundstrand Company Fuel Metering Valves XVG User Manual

Page 9

background image

Example: Request to write 0x03 to register 2.

Request Response
01 06 00 01 00 03 98 0B

01 06 00 01 00 03 98 0B

Function 06

Function 06

Register Address Hi 00

Register Address Hi 00

Register Address Lo 01

Register Address Lo 01

Register Value Hi 00

Register Value Hi 00

Register Value Lo 03

Register Value Lo 03

CRC 98 0B

CRC 98 0B

Table 9: Modbus Function 06 – Example



7.4.3 Write Multiple Registers (0x10)

Request message:
SLAVE ADDRESS + FUNCTION CODE + STARTING ADDRESS + QUANTITY
OF REGISTERS + BYTES COUNT + REGISTERS VALUES + CRC

Request

Length Valid

Value

Slave Address

1 Byte

0 to 247

Function code

1 Byte

0x10

Starting Address

2 Bytes

0x0000 to 0xFFFF

Quantity of Registers

2 Bytes

1 to 123 (0x7B)

Bytes count

1 Byte

2xN

Registers Values

2xN Bytes

value

CRC 2

Bytes

0x0000 to 0xFFFF

*N = Quantity of Registers

Table 10: Modbus Function 16 - Request Message


Response message:
SLAVE ADDRESS + FUNCTION CODE + STARTING ADDRESS + QUANTITY
OF REGISTERS + CRC

Response

Length Valid

Value

Slave Address

1 Byte

0 to 247

Function code

1 Byte

0x10

Starting Address

2 Bytes

0x0000 to 0xFFFF

Quantity of Registers

2 Bytes

1 to 123 (0x7B)

CRC 2

Bytes

0x0000 to 0xFFFF

Table 11: Modbus Function 16 - Response Message


Example: Write 0x0A and 0x0102 to two registers, starting at register 2.

Request Response
01 10 00 01 00 02 04 00 0A 01 02 92 30

01 10 00 01 00 02 10 08

Function 10

Function 10

9

This manual is related to the following products: