2 position interpolation parameters, Position interpolation parameters – Hamilton Sundstrand Company Fuel Metering Valves XVG User Manual
Page 17
Register
Number
XVG/eXVG Parameter
Name
Write
Access
Description Type
Default
Value
7650 7651
IDM_AO0CUROFF
W4
AO0 Current Offset: range -4 to 4 counts
Float
0
7652 7653
IDM_AO0VOLTGAIN
W4
AO0 Voltage Gain: range 0.72 – 0.80
Float
1
7654 7655
IDM_AO0VOLTOFF
W4
AO0 Voltage Offset: range -4 to 4 counts
Float
0
7656 7657
IDM_AO1CURGAIN
W4
AO1 Current Gain: range 0.72 – 0.80
Float
1
7658 7659
IDM_AO1CUROFF
W4
AO1 Current Offset: range -4 to 4 counts
Float
0
7660 7661
IDM_AO1VOLTGAIN
W4
AO1 Voltage Gain: range 0.72 – 0.80
Float
1
7662 7663
IDM_AO1VOLTOFF
W4
AO1 Voltage Offset: range -4 to 4 counts
Float
0
7664 7665
IDM_AO2CURGAIN
W4
AO2 Current Gain: range 0.72 – 0.80
Float
1
7666 7667
IDM_AO2CUROFF
W4
AO2 Current Offset: range -4 to 4 counts
Float
0
7668 7669
IDM_AO2VOLTGAIN
W4
AO2 Voltage Gain: range 0.72 – 0.80
Float
1
7670 7671
IDM_AO2VOLTOFF
W4
AO2 Voltage Offset: range -4 to 4 counts
Float
0
7672 7673
IDM_AI0VOLTGAIN
W4
AI0 Voltage Gain: range 1.03 – 1.05
Float
1
7674 7675
IDM_AI0VOLTOFF
W4
AI0 Voltage Offset: range -(122.6 to 146.6)
Float
0
7676 7677
IDM_AI1VOLTGAIN
W4
AI1 Voltage Gain: range 1.03 – 1.05
Float
1
7678 7679
IDM_AI1VOLTOFF
W4
AI1 Voltage Offset: range -(122.6 to 146.6)
Float
0
7680 7681
IDM_AI2VOLTGAIN
W4
AI2 Voltage Gain: range 1.03 – 1.05
Float
1
7682 7683
IDM_AI2VOLTOFF
W4
AI2 Voltage Offset: range -(122.6 to 146.6)
Float
0
7684 7685
IDM_AI3VOLTGAIN
W4
AI3 Voltage Gain: range 1.03 – 1.05
Float
1
7686 7687
IDM_AI3VOLTOFF
W4
AI3 Voltage Offset: range -(122.6 to 146.6)
Float
0
7688 7689
IDM_AI4VOLTGAIN
W4
AI4 Voltage Gain: range 1.03 – 1.05
Float
1
7690 7691
IDM_AI4VOLTOFF
W4
AI4 Voltage Offset: range -(122.6 to 146.6)
Float
0
7692 7693
IDM_AI5VOLTGAIN
W4
AI5 Voltage Gain: range 1.03 – 1.05
Float
1
7694 7695
IDM_AI5VOLTOFF
W4
AI5 Voltage Offset: range -(122.6 to 146.6)
Float
0
7696 7697
IDM_OVERPRESLIM
W4
Overpressure Limit, range 200 to 600PSIA
Float
450
7698 7699
IDM_MAXINTERR
W4
Maximum integral position control
contribution, units of velocity. Range 0.0 to
1.999
Float
0.0000
13
7700 7701
IDM_TR
W4
Thermal aging reference temperature, units of
deg C. Range: 0.0 to 150.0
Float
60.0
7702 7703
IDM_TITDB
W4
Total inches traveled accumulator dead-band,
units of inches. Range: 0.0 to 0.005
Float
0.0005
7704 7705
IDM_INPRESCOEF2
W4
Second order inlet pressure sensor correction
coefficient. Range: -1.0 to 1.0
Float
0.0
7706 7707
IDM_OUTPRESCOEF2
W4
Second order inlet pressure sensor correction
coefficient. Range: -1.0 to 1.0
Float
0.0
Table 16: General Setup Parameters
9.1.2 Position Interpolation Parameters
The XVG/eXVG Fuel Metering Valve can be configured to operate with a non-linear
stroke profile by adjusting the values in this table. The Position Interpolation Table is a
43-point table, which maps a specific position to a linear demand position point. The first
30 points in the table are spaced at 0.1mA intervals and the remaining points are spaced
at 1.0mA intervals.
17