2 position interpolation parameters, Position interpolation parameters – Hamilton Sundstrand Company Fuel Metering Valves XVG User Manual

Page 17

background image

Register
Number

XVG/eXVG Parameter

Name

Write

Access

Description Type

Default

Value

7650 7651

IDM_AO0CUROFF

W4

AO0 Current Offset: range -4 to 4 counts

Float

0

7652 7653

IDM_AO0VOLTGAIN

W4

AO0 Voltage Gain: range 0.72 – 0.80

Float

1

7654 7655

IDM_AO0VOLTOFF

W4

AO0 Voltage Offset: range -4 to 4 counts

Float

0

7656 7657

IDM_AO1CURGAIN

W4

AO1 Current Gain: range 0.72 – 0.80

Float

1

7658 7659

IDM_AO1CUROFF

W4

AO1 Current Offset: range -4 to 4 counts

Float

0

7660 7661

IDM_AO1VOLTGAIN

W4

AO1 Voltage Gain: range 0.72 – 0.80

Float

1

7662 7663

IDM_AO1VOLTOFF

W4

AO1 Voltage Offset: range -4 to 4 counts

Float

0

7664 7665

IDM_AO2CURGAIN

W4

AO2 Current Gain: range 0.72 – 0.80

Float

1

7666 7667

IDM_AO2CUROFF

W4

AO2 Current Offset: range -4 to 4 counts

Float

0

7668 7669

IDM_AO2VOLTGAIN

W4

AO2 Voltage Gain: range 0.72 – 0.80

Float

1

7670 7671

IDM_AO2VOLTOFF

W4

AO2 Voltage Offset: range -4 to 4 counts

Float

0

7672 7673

IDM_AI0VOLTGAIN

W4

AI0 Voltage Gain: range 1.03 – 1.05

Float

1

7674 7675

IDM_AI0VOLTOFF

W4

AI0 Voltage Offset: range -(122.6 to 146.6)

Float

0

7676 7677

IDM_AI1VOLTGAIN

W4

AI1 Voltage Gain: range 1.03 – 1.05

Float

1

7678 7679

IDM_AI1VOLTOFF

W4

AI1 Voltage Offset: range -(122.6 to 146.6)

Float

0

7680 7681

IDM_AI2VOLTGAIN

W4

AI2 Voltage Gain: range 1.03 – 1.05

Float

1

7682 7683

IDM_AI2VOLTOFF

W4

AI2 Voltage Offset: range -(122.6 to 146.6)

Float

0

7684 7685

IDM_AI3VOLTGAIN

W4

AI3 Voltage Gain: range 1.03 – 1.05

Float

1

7686 7687

IDM_AI3VOLTOFF

W4

AI3 Voltage Offset: range -(122.6 to 146.6)

Float

0

7688 7689

IDM_AI4VOLTGAIN

W4

AI4 Voltage Gain: range 1.03 – 1.05

Float

1

7690 7691

IDM_AI4VOLTOFF

W4

AI4 Voltage Offset: range -(122.6 to 146.6)

Float

0

7692 7693

IDM_AI5VOLTGAIN

W4

AI5 Voltage Gain: range 1.03 – 1.05

Float

1

7694 7695

IDM_AI5VOLTOFF

W4

AI5 Voltage Offset: range -(122.6 to 146.6)

Float

0

7696 7697

IDM_OVERPRESLIM

W4

Overpressure Limit, range 200 to 600PSIA

Float

450

7698 7699

IDM_MAXINTERR

W4

Maximum integral position control
contribution, units of velocity. Range 0.0 to
1.999

Float

0.0000

13

7700 7701

IDM_TR

W4

Thermal aging reference temperature, units of
deg C. Range: 0.0 to 150.0

Float

60.0

7702 7703

IDM_TITDB

W4

Total inches traveled accumulator dead-band,
units of inches. Range: 0.0 to 0.005

Float

0.0005

7704 7705

IDM_INPRESCOEF2

W4

Second order inlet pressure sensor correction
coefficient. Range: -1.0 to 1.0

Float

0.0

7706 7707

IDM_OUTPRESCOEF2

W4

Second order inlet pressure sensor correction
coefficient. Range: -1.0 to 1.0

Float

0.0

Table 16: General Setup Parameters


9.1.2 Position Interpolation Parameters

The XVG/eXVG Fuel Metering Valve can be configured to operate with a non-linear
stroke profile by adjusting the values in this table. The Position Interpolation Table is a
43-point table, which maps a specific position to a linear demand position point. The first
30 points in the table are spaced at 0.1mA intervals and the remaining points are spaced
at 1.0mA intervals.

17