0.3 DECALS (continued)

7

WARNING

!

Hazardous voltage. Can cause
severe injury or death.

Only use factory supplied inlet for
incoming power. See Operators/
Instruction manual.

WARNING

!

Hazardous voltage. Can cause
severe injury or death.

Disconnect power before servicing.
Lockout/Tagout machine.

Electrical

power inlet.

VOLTAGE DECAL OPTION
INSIDE STARTER BOX
ON RIGHT SIDE

SCHEMATIC DECAL

54425996 Rev. C (75-160 KW) - 2 REQUIRED

39543764 Rev. 04

39540174 Rev. 05

39541354 Rev 03

Instruction Manual.

WARNING

!

Hazardous voltage. Can cause
severe injury or death.

Only use factory supplied inlet for
incoming power. See Operators/
Instruction manual.

39543764 Rev. 03

Instruction Manual.

Compressor Package Data

COMPRESSOR MODEL...............................
CAPACITY......................................................
RATED OPERATING PRESSURE.................
MAX. DISCHARGE PRESSURE...................
MAX. MODULATE PRESSURE.....................
NOMINAL DRIVE MOTOR............................
NOMINAL FAN MOTOR................................
TOTAL PACKAGE AMPS...............................
VOLTS............................................................
PHASE / HERTZ............................................
CONTROL VOLTAGE.....................................
SERIAL NUMBER..........................................

CONTACTOR AMP. RATING.....................................
ASSEMBLY AMP. RATING........................................
LOCKED ROTOR AMP. RATING OF ASSY. ............

AIR SOLUTIONS GROUP

DAVIDSON, NORTH CAROLINA 28036

WWW.AIR.INGERSOLL-RAND.COM

54425996 Rev.C

m3/MIN
BARG
BARG
BARG
KW
KW

39921804 Rev. B

NOTICE

IEC Starter Overload Setting

1. Full-Voltage Starter (Main or Fan Motor):

Multiply MOTOR nameplate amps by 1.11.

Star-Delta Starter (Main motors only):
Multiply MOTOR nameplate amps by 0.64.

2. Set corresponding overload relay at

this value.

3. Never exceed the following limits:

Full-Voltage Starter: 125% of MOTOR
nameplate amps.

Star-Delta Starter: 72% of MOTOR
nameplate amps.

39557095 Rev.05 (100-200 HP) - 2 REQUIRED

Compressor Package Data

COMPRESSOR MODEL...............................
CAPACITY......................................................
RATED OPERATING PRESSURE.................
MAX. DISCHARGE PRESSURE...................
MAX. MODULATE PRESSURE.....................
NOMINAL DRIVE MOTOR............................
NOMINAL FAN MOTOR................................
TOTAL PACKAGE AMPS...............................
VOLTS............................................................
PHASE / HERTZ............................................
CONTROL VOLTAGE.....................................
SERIAL NUMBER..........................................

CONTACTOR AMP. RATING.....................................
ASSEMBLY AMP. RATING........................................
LOCKED ROTOR AMP. RATING OF ASSY. ............

AIR SOLUTIONS GROUP

DAVIDSON, NORTH CAROLINA 28036

WWW.AIR.INGERSOLL-RAND.COM

39557095 Rev.05

CFM
PSIG
PSIG
PSIG
H.P.
H.P.

This manual is related to the following products: