beautypg.com

High voltage, Inlet outlet – Goodman Mfg GAS-FIRED WARM AIR FURNACE GKS9 User Manual

Page 30

background image

30

2. Remove the burner compartment door and move the furnace

gas valve manual control to the OFF position.

3. Close the manual gas shutoff valve external to the furnace.
4. Replace the burner compartment door.

G

AS

S

UPPLY

P

RESSURE

M

EASUREMENT

CAUTION

T

O

 

PREVENT

 

UNRELIABLE

 

OPERATION

 

OR

 

EQUIPMENT

 

DAMAGE

THE

 

INLET

 

GAS

 

SUPPLY

 

PRESSURE

 

MUST

 

BE

 

AS

 

SPECIFIED

 

ON

 

THE

 

UNIT

 

RATING

 

PLATE

 

WITH

 

ALL

 

OTHER

 

HOUSEHOLD

 

GAS

 

FIRED

 

APPLIANCES

 

OPERATING

.

HIGH VOLTAGE !

D

ISCONNECT

 

ALL

 

POWER

 

BEFORE

 

SERVICING

 

OR

 

INSTALLING

 

THIS

 

UNIT

. M

ULTIPLE

 

POWER

 

SOURCES

 

MAY

 

BE

 

PRESENT

. F

AILURE

 

TO

 

DO

 

SO

 

MAY

 

CAUSE

 

PROPERTY

 

DAMAGE

PERSONAL

 

INJURY

 

OR

 

DEATH

.

WARNING

The line pressure supplied to the gas valve must be within the
range specified below. The supply pressure can be measured at
the gas valve inlet pressure tap or at a hose fitting installed in the
gas piping drip leg. The supply pressure must be measured with
the unit OFF. To measure inlet pressure, use the following proce-
dure.

Pressure Regulator

Adjustment

(Under Cap Screw)

Gas Valve

On/Off

Selector

Switch

INLET

OUTLET

Inlet Pressure

Tap

Outlet Pressure

Tap

White-Rodgers Model 36G22

Gas Valve On/Off
Selector Switch

Inlet
Pressure
Tap

Pressure Regulator
(under cap screw)

Outlet
Pressure
Tap

Honeywell Model VR8215 (Single-Stage)

1.

Turn OFF gas to furnace at the manual gas shutoff valve
external to the furnace.

2.

Turn OFF all electrical power to the system.

3.

Inlet pressure tap connections:

a.

Honeywell VR8215 Valve:
Remove the inlet pressure boss plug. Install an 1/8” NPT
hose barb fitting into the outlet pressure tap.

b.

White-Rodgers 36G22 valve:
Back inlet pressure test screw (inlet pressure boss) out
one turn (counterclockwise, not more than one turn).

4.

Attach a hose and manometer to the outlet pressure barb
fitting (Honeywell valve) or inlet pressure boss (White-
Rodgers valve).

5.

Turn ON the gas supply.

6.

Turn On power and close thermostat “R” and “W” contacts
to provide a call for heat.

7.

Using a leak detection solution or soap suds, check for
leaks at outlet pressure boss plug (Honeywell valve) or
screw (White-Rodgers valve). Bubbles forming indicate a
leak. SHUT OFF GAS AND REPAIR ALL LEAKS
IMMEDIATELY!

8.

Measure the gas supply pressure with burners firing. Adjust
supply pressure using the Inlet Gas Supply Pressure table
shown below. If supply pressure reading differs from the
table, make necessary adjustments to pressure regulator,
gas piping size, etc., and/or consult with local gas utility.

Natural Gas

Minimum: 4.5" W.C. Maximum: 10.0" W.C.

Propane Gas

Minimum: 11.0" W.C. Maximum: 13.0" W.C.

Inlet Gas Supply Pressure

9.

Turn OFF all electrical power and gas supply to the system.

10. Remove the manometer hose from the hose barb fitting or

inlet pressure boss.

11. Replace inlet pressure tap:

a.

Honeywell VR8215 valve:
Remove the 1/8” NPT hose barb fitting from the inlet
pressure tap. Replace the inlet pressure boss plug and
seal with a high quality thread sealer.

b.

White-Rodgers 36G22 valve:
Turn inlet pressure test screw in to seal pressure port
(clockwise, 7 in-lb minimum).

12. Retest for leaks. If bubbles form, shut down gas and repair

leaks immediately.

13. Turn ON electrical power and gas supply to the system.
14. Turn valve switch ON.

G

AS

M

ANIFOLD

P

RESSURE

M

EASUREMENT

AND

A

DJUSTMENT

T

O

 

PREVENT

 

UNRELIABLE

 

OPERATION

 

OR

 

EQUIPMENT

 

DAMAGE

THE

 

GAS

 

MANIFOLD

 

PRESSURE

 

MUST

 

BE

 

AS

 

SPECIFIED

 

ON

 

THE

 

UNIT

 

RATING

 

PLATE

. O

NLY

 

MINOR

 

ADJUSTMENTS

 

SHOULD

 

BE

 

MADE

 

BY

 

ADJUSTING

 

THE

 

GAS

 

VALVE

 

PRESSURE

 

REGULATOR

.

CAUTION