beautypg.com

24 v, Warning, Caution – Goodman Mfg GAS-FIRED WARM AIR FURNACE GKS9 User Manual

Page 24

background image

24

*

*

*

*

*

*

*

*

*

STANDARD

JUNCTION BOX

LOCATION

ALTERNATE

JUNCTION BOX

LOCATION

Junction Box Relocation

HIGH VOLTAGE!
T

O

AVOID

THE

RISK

OF

INJURY

,

ELECTRICAL

SHOCK

OR

DEATH

,

THE

FURNACE

MUST

BE

ELECTRICALLY

GROUNDED

IN

ACCORDANCE

WITH

LOCAL

CODES

OR

IN

THEIR

ABSENCE

,

WITH

THE

LATEST

EDITION

OF

THE

N

ATIONAL

E

LECTRIC

C

ODE

.

WARNING

To ensure proper unit grounding, the ground wire should run from
the furnace ground screw located inside the furnace junction box
all the way back to the electrical panel. NOTE: Do not use gas
piping as an electrical ground. To confirm proper unit grounding,
turn off the electrical power and perform the following check.

1. Measure resistance between the neutral (white) connection

and one of the burners.

2. Resistance should measure 10 ohms or less.

This furnace is equipped with a blower door interlock switch which
interrupts unit voltage when the blower door is opened for servic-
ing. Do not defeat this switch.

24 V

OLT

T

HERMOSTAT

W

IRING

NOTE: Wire routing must not interfere with circulator blower
operation, filter removal, or routine maintenance.

Low voltage connections can be made through either the right or
left side panel. Thermostat wiring entrance holes are located adja-
cent to the junction box locations in the blower compartment. Wire
routing must not to interfere with circulator blower operation, filter
removal, or routine maintenance. Refer to the following figure for
thermostat connections to the integrated control module terminal
strip.

W

W

W

Y

Y

Y

C

C

R

R

R

G

G

W

Y

C

R

G

HEATING

ROOM

THERMOSTAT

HEATING AND

COOLING ROOM

THERMOSTAT

FURNACE

FURNACE

REMOTE

CONDENSING

UNIT

Thermostat Diagram

This furnace is equipped with a 40 VA transformer to facilitate use
with most cooling equipment. Consult the wiring diagram, located
on the blower compartment door, for further details of 115 Volt and
24 Volt wiring.

24 V

OLT

H

UMIDIFIER

The yellow wire connected to the I.D. Blower pressure switch is
powered anytime the pressure switch is closed and provides 24
VAC humidifier control. Remove the yellow wire and connect a field
supplied jumper wire with a “piggyback” terminal to the pressure
switch terminal. Reconnect the yellow wire to the “piggyback” ter-
minal on the jumper wire and then connect the 24 VAC line of the
humidifier to the stripped end of the jumper wire. Using a wire nut
or a field-supplied quick connect terminal can make this connec-
tion. The wiring must conform to all local and national codes. Con-
nect the COM side of the humidifier to the B/C terminal on the
furnace control board (or to the COM side of the 24 VAC trans-
former). DO NOT CONNECT 115V HUMIDIFIER TO THESE TERMI-
NALS.

XII. GAS SUPPLY AND PIPING

G

ENERAL

The furnace rating plate includes the approved furnace gas input
rating and gas types. The furnace must be equipped to operate on
the type of gas applied. This includes any conversion kits required
for alternate fuels and/or high altitude.

T

O

PREVENT

UNRELIABLE

OPERATION

OR

EQUIPMENT

DAMAGE

,

THE

GAS

MANIFOLD

PRESSURE

MUST

BE

AS

SPECIFIED

ON

THE

UNIT

RATING

PLATE

. O

NLY

MINOR

ADJUSTMENTS

SHOULD

BE

MADE

BY

ADJUSTING

THE

GAS

VALVE

PRESSURE

REGULATOR

.

CAUTION

Inlet gas supply pressures must be maintained within the ranges
specified below. The supply pressure must be constant and avail-
able with all other household gas fired appliances operating. The
minimum gas supply pressure must be maintained to prevent
unreliable ignition. The maximum must not be exceeded to pre-
vent unit overfiring.

Natural Gas

Minimum: 4.5" W.C. Maximum: 10.0" W.C.

Propane Gas

Minimum: 11.0" W.C. Maximum: 13.0" W.C.

Inlet Gas Supply Pressure

H

IGH

A

LTITUDE

D

ERATE

When this furnace is installed at high altitude, the appropriate High
Altitude orifice kit must be applied. This is required due to the
natural reduction in the density of both the gas fuel and combus-
tion air as altitude increases. The kit will provide the proper design
certified input rate within the specified altitude range.
High altitude kits are purchased according to the installation alti-
tude and usage of either natural or propane gas. Contact your
distributor for a tabular listing of appropriate altitude ranges and
corresponding manufacturer’s high altitude (Natural, Propane Gas,
and/or Pressure Switch) kits.
Do not derate the furnace by adjusting the manifold pressure to a
lower pressure than specified on the furnace rating plate. The
combination of the lower air density and a lower manifold pressure
will prohibit the burner orifice from drawing the proper amount of
air into the burner. This may cause incomplete combustion, flash-
back, and possible yellow tipping.
In some areas the gas supplier may artificially derate the gas in an
effort to compensate for the effects of altitude. If the gas is artifi-
cially derated, the appropriate orifice size must be determined
based upon the BTU/ft

3

content of the derated gas and the altitude.