2. Low Ice Production

PROBLEM

POSSIBLE CAUSE

REMEDY

[1] Abnormal refrigeration

circuit.

a) Condenser

1. Dirty air filter or

condenser.

1. Clean.

2. Bad ventilation.

2. Remove anything blocking

vents.

b) Thermostatic Expansion

Valve

1. Low-side pressure or

temperature exceeding
the limit.

1. Secure bulb to low-side line

or replace.

c) Refrigerant Lines

1. Gas leaks.

1. Check for leaks with a leak

detector. Reweld leak,
replace drier and charge
with refrigerant. The amount
of refrigerant is marked on
the nameplate.

2. Overcharged.

2. Recharge.

d) Compressor Motor

Protector

1. Overload protector

stops compressor
intermittently.

1. Check condenser and fan

motor.

e) Inside Wall of Evaporator 1. Scale on inside wall of

freezing cylinder.

1. Remove auger, use

Hoshizaki "Scale Away" or
"LIME-A-WAY" solution to
clean periodically.

If water is found to exceed
the following levels, install a
conditioner:
Hardness 50 ppm
Silica 30 ppm

[2]

a) Condenser

1. Dirty air filter or

condenser.

1. Clean.

2. Bad ventilation.

2. Remove anything blocking

vents.

3. Ambient temperature

too high.

3. Check ventilation and

location, and change as
needed.

4. Less than 6" clearance

at rear, sides and top.

4. Allow proper clearance for

ventilation.

b) Fan Motor

1. Fan revolving too

slowly.

1. See chart 1,[5], a)

[3] Poor water flow.

a) Water Supply

1. Water pressure too low. 1. See chart 1,[6], a)

Condensing
temperature too high.